Bryant FF1DNA Fan User Manual


 
4
SPECIFICATIONS
See notes on page 5.
UNITS WITHOUT ELECTRIC HEATERS OR CONTROLS
UNIT SIZE 0180 0240 0300
RATINGS & PERFORMANCES
Nominal Capacity (Btuh)* 18,000 24,000 30,000
Nominal Airow (CFM) 650 870 1080
ELECTRICAL
Unit Volts-Phase (60 Hz) 208/2301 208/2301 208/2301
Operating Voltage Range 187253 187253 187253
Internal Circuit Protection None
Minimum Ampacity for Wire Sizing
Minimum Wire Size 14
Maximum Fuse Size (Amps or Ckt Bkr) 15
Control Transformer 24V (Va)
INDOOR COIL
Rows & Fins Per In. 2 & 14 3 & 14
Height x Width (In.) 18 x 17.8 22 x 17.8
Face Area (Sq Ft) 2.23 2.72
R-22 Refrigerant Metering DeviceFF1DNA Check-Flo-Rater
R-22 Refrigerant Metering DeviceFF1DNE TXV
Piston Number 55 63 70
Condensate Drain Connection (Pri-Sec) 3/4 FPT
INDOOR BLOWER & MOTOR
Wheel Diameter x Width (In.) 10 x 6
Filter SizeCleanable (In.) 16 x 20 x 1
Blower Motor HP 1/12 1/5 1/3
Blower Motor Speeds & Type 2 & PSC 2 & PSC 2 & PSC
Full Load Amps 0.7 1.5 2.0
OPTIONAL EQUIPMENT
Cooling Control Relay-Transformer Package
(with TDR)
KFDCC0101DCC
Louvered Wall Panel with Frame (6 Pack) KFBLG0106LGL
Electric Heat Package See ‘‘Optional Field-Installed Electric Heat Packages’’ Table
UNITS WITH FACTORY-INSTALLED ELECTRIC HEATERS OR CONTROLS
SIZES 018005 018075 018011††
RATINGS & PERFORMANCES
Nominal Capacity (Btuh)* 18,000 18,000 18,000
Nominal Airow (CFM) 650 650 650
Electric Heating Output (kw @240v) 5.0 7.5 11.0
Electric Heating Capacity (MBH @208/230v) 13.5/16.3 19.9/24.2 28.9/35.1
ELECTRICAL
Unit Volts-Phase (60 Hz) 208/2301 208/2301 208/2301
Operating Voltage Range 187253 187253 187253
Internal Circuit Protection None
Full Load Amps 18.1/20.0 27.1/30.0 39.8/44.0
Minimum Ampacity for Wire Sizing 23.5/25.9 34.8/38.4 50.6/55.9
Minimum Wire Size 10/10 8/8 6/6
Maximum Wire Length (Ft) 112/112 118/118 125/125
Maximum Fuse Size (Amps or Ckt Bkr) 25/30 35/40 60/60
Control Transformer 24V (VA) 40
INDOOR COIL
Rows & Fins Per In. 2 & 14
Height x Width (In.) 18 x 17.8
Face Area (Sq Ft) 2.23
R-22 Refrigerant Metering DeviceFF1DNA Check-Flo-Rater
R-22 Refrigerant Metering DeviceFF1DNE TXV
Piston Number 55
Condensate Drain Connection (Pri-Sec) 3/4 FPT
INDOOR BLOWER & MOTOR
Wheel Diameter x Width (In.) 10 x 6
Filter SizeCleanable (In.) 16 x 20 x 1
Blower Motor HP 1/12
Blower Motor Speeds & Type 2 (PSC)
Full Load Amps 0.7
OPTIONAL EQUIPMENT
Louvered Wall Panel with Frame (6 Pack) KFBLG0106LGL
Electric Heat Package See ‘‘Optional Field-Installed Electric Heat Packages’’ Table