Bryant 579F Gas Heater User Manual


 
240
PERFORMANCE DATA (cont)
COOLING CAPACITIES — STANDARD UNITS (cont)
LEGEND
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
t
lwb
= Wet-bulb temperature corresponding to enthalpy of air leaving evapo-
rator coil (h
lwb
)
Where: h
ewb
= Enthalpy of air entering evaporator coil
3. The SHC is based on 80 F edb temperature of air entering evaporator coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).
4. Use chart below for bypass factor.
581A180 (15 Tons)
Temp (F)
Air Ent
Cond
Evap Air — Cfm/BF
4500/0.01 5250/0.01 6000/0.01
Evap Air — Ewb (F)
54 58 62 67 72 76 80 54 58 62 67 72 76 80 54 58 62 67 72 76 80
60
TC 180.5 184.6 188.7 203.5 219.9 233.7 247 189.3 191.7 194.2 208.7 224.1 238 251 198.1 198.8 199.6 212.9 229.3 242 255
SHC 180.5 172.4 159.4 132.3 104.7 87.9 65.7 189.3 183.2 173.2 142.8 110.4 91 65.5 198.1 195.1 185.1 153.1 116.7 94 65.4
kW 9.41 9.49 9.58 9.87 10.19 10.47 10.78 9.58 9.63 9.68 9.97 10.29 10.57 10.87 9.75 9.77 9.79 10.07 10.39 10.67 10.95
70
TC 176.7 180.5 184.4 199 215.1 227.8 242 185.3 187.5 189.8 203 219.2 231.8 245 193 194.5 195.1 208.1 224.3 237 248
SHC 176.7 169 155.8 129.4 102.4 86 63.9 185.3 179.7 169.3 138.9 108 89.1 63.8 193 191.4 181 149.7 114.2 92.2 63.7
kW 10.5 10.57 10.64 10.96 11.35 11.62 11.95 10.68 10.72 10.76 11.06 11.45 11.72 12.04 10.85 10.87 10.89 11.17 11.55 11.82 12.13
75
TC 174.7 177.5 181 196 213 224.2 238 182.3 184.4 186 201 217 229.2 242 190.9 191.3 189 204 219 233.1 246
SHC 174.7 167.2 147 124 99 84.9 62.9 182.3 177.9 160 133 105 88 62.8 190.9 189.5 173 143 113 91 62.7
kW 11.07 11.14 11.2 11.6 12 12.23 12.57 11.25 11.3 11.3 11.7 12.1 12.33 12.66 11.45 11.45 11.4 11.8 12.1 12.44 12.75
85
TC 169.6 172.2 175 190 205 218.1 230.8 177.2 179 180 194 209 221.9 233.3 185.6 185.9 183 198 212 225.7 237
SHC 169.6 163.3 145 121 97 82.5 60.7 177.2 174.1 157 130 102 85.6 60.5 185.6 184.7 168 139 106 88.6 60.4
kW 12.29 12.35 12.3 12.7 13.1 13.5 13.86 12.47 12.51 12.5 12.8 13.2 13.61 13.96 12.67 12.68 12.6 12.9 13.3 13.71 14.05
95
TC 164.3 166.5 168 182 197 209.8 221.2 171.7 172.6 172 187 201 213.4 224.6 179.1 179.3 176 190 203 217.1 228
SHC 164.3 158.9 142 118 93 79.8 57.9 171.7 168.8 154 127 98 82.8 57.9 179.1 178.7 164 136 102 86 57.8
kW 13.59 13.65 13.5 13.9 14.3 14.85 15.23 13.8 13.82 13.6 14 14.4 14.96 15.32 14 14 13.8 14.1 14.5 15.07 15.43
105
TC 158.1 159.8 161 174 188 200.3 212.4 165.2 166 165 178 191 203.8 214.6 172.3 172.3 169 181 193 207.3 216.8
SHC 158.1 154.2 138 115 91 76.8 55.2 165.2 163.1 150 124 95 79.9 55.1 172.3 172.2 158 132 98 83 54.9
kW 14.97 15.02 14.8 15.2 15.6 16.28 16.69 15.19 15.21 14.9 15.3 15.7 16.39 16.77 15.41 15.4 15.1 15.4 15.7 16.5 16.86
115
TC 151.8 152.8 152 165 179 190.6 201.3 158.4 158.8 157 168 180 194 204.5 165 164.9 161 171 181 197.3 206.6
SHC 151.8 149.1 134 111 87 73.7 52.1 158.4 157 145 120 91 76.7 52.1 165 164.9 151 128 94 79.8 51.9
kW 16.45 16.48 16.1 16.5 16.9 17.79 18.21 16.68 16.68 16.2 16.6 17 17.91 18.3 16.89 16.88 16.4 16.7 17 18.01 18.39
125
TC 144.7 145.4 146 157.1 170.5 180.7 191.1 150.8 151.1 151.5 160.2 172.9 183.9 192 156.8 156.9 157 163.2 175.4 186.2 193.9
SHC 144.7 143.5 123.4 102.2 81.16 70.4 48.9 150.8 150.2 135.2 109.6 85.15 73.4 48.8 156.8 156.9 145.6 117.4 89.3 76.4 48.7
kW 17.96 18.01 18.05 18.49 18.99 19.44 19.85 18.18 18.22 18.25 18.6 19.11 19.5 19.89 18.42 18.44 18.46 18.72 19.14 19.65 19.93
581A180 (15 Tons) (cont)
Temp (F)
Air Ent
Cond
Evap Air — Cfm/BF
6750/0.01 7500/0.02
Evap Air — Ewb (F)
54 58 62 67 72 76 80 54 58 62 67 72 76 80
60
TC 203.8 204.2 204.6 216.3 231.7 244 257 209.5 209.5 209.6 218.8 235 248 259
SHC 203.8 201.8 191.2 164.1 124.1 97 65.4 209.5 209.5 196.6 173.7 138.1 100 65.2
kW 9.88 9.88 9.89 10.13 10.45 10.72 11 9.99 9.99 9.99 10.19 10.51 10.78 11.05
70
TC 199.6 199.8 200.1 210.5 226.5 239 250 205.2 205.1 205.1 213.8 228.8 241 252
SHC 199.6 197.8 187 159.7 121.3 95.2 63.5 205.2 205.1 192.4 169.8 134.5 98.2 63.5
kW 10.99 10.99 11 11.24 11.6 11.88 12.18 11.12 11.11 11.11 11.31 11.65 11.94 12.22
75
TC 196.4 196.6 194 206 220 235 247 201.9 201.9 198 208 223 237 249
SHC 196.4 195.7 181 153 120 94 62.5 201.9 201.9 186 163 163 97.1 62.5
kW 11.58 11.58 11.6 11.9 12.2 12.5 12.8 11.71 11.7 11.7 11.9 11.9 12.56 12.84
85
TC 191 191.1 188 200 213 227.8 239 196.4 196.4 192 202 214 229.8 241
SHC 191 190.5 175 148 115 91.6 60.2 196.4 196.4 180 157 119 94.6 60.2
kW 12.81 12.81 12.7 13 13.3 13.77 14.1 12.96 12.95 12.8 13.1 13.4 13.84 14.13
95
TC 184.4 184.5 181 192 205 219.1 229.7 189.7 189.7 185 194 206 221.1 230.5
SHC 184.4 184.2 170 144 108 88.9 57.7 189.7 189.7 174 153 113 91.9 57.6
kW 14.15 14.15 13.9 14.2 14.6 15.14 15.47 14.29 14.29 14 14.3 14.6 15.2 15.51
105
TC 176.7 176.7 173 182 194 209.2 218.5 181.9 181.9 177 184 194 211.1 220.1
SHC 176.7 176.7 162 140 103 86 54.9 181.9 181.9 166 148 107 88.9 54.7
kW 15.55 15.55 15.2 15.5 15.8 16.57 16.9 15.7 15.7 15.3 15.5 15.8 16.64 16.94
115
TC 169.5 169.4 166 172 183 198.2 207.1 173.9 173.8 169 174 183 200 208.6
SHC 169.5 169.4 155 136 98 82.7 51.8 173.9 173.8 158 142 101 85.6 51.7
kW 17.05 17.04 16.6 16.8 17.1 18.08 18.42 17.2 17.2 16.7 16.9 17.1 18.15 18.45
125
TC 160.9 161.1 161.2 165.6 177.4 187.9 195.4 165.1 165.2 165.4 167.8 179.2 188.6 196
SHC 160.9 161.1 150.7 125.6 95.04 79.4 48.7 165.1 165.2 155.2 133.2 105.3 82.3 48.6
kW 18.57 18.59 18.62 18.81 19.18 19.68 20.06 18.72 18.75 18.78 18.91 19.33 19.71 20.09
BF Bypass Factor
Edb Entering Dry-Bulb
Ewb Entering Wet-Bulb
kW Compressor Motor Power Input
ldb Leaving Dry-Bulb
lwb Leaving Wet-Bulb
SHC Sensible Heat Capacity (1000 Btuh) Gross
TC Total Capacity (1000 Btuh) Gross
t
ldb
= t
edb
sensible capacity (Btuh)
1.10 x cfm
h
lwb
= h
ewb
total capacity (Btuh)
4.5 x cfm
BYPASS
FACTOR
(BF)
ENTERING AIR DRY-BULB TEMP (F)
79 78 77 76 75 under 75
81 82 83 84 85 over 85
Correction Factor
.05 1.04 2.07 3.11 4.14 5.18
Use formula
shown below.
.10 .98 1.96 2.94 3.92 4.90
.20 .87 1.74 2.62 3.49 4.36
.30 .76 1.53 2.29 3.05 3.82
CFM
ENTERING WET-BULB (F)
54 58 62 67 72 76 80
Bypass Factor
4500 0.396 0.193 0.054 0.053 0.067 0.000 0.000
5250 0.455 0.272 0.077 0.065 0.077 0.000 0.000
6000 0.504 0.337 0.121 0.077 0.088 0.000 0.000
6750 0.544 0.390 0.193 0.094 0.100 0.000 0.000
7500 0.578 0.436 0.244 0.108 0.114 0.000 0.000