Bryant 574B Gas Heater User Manual


 
9
BASE UNIT DIMENSIONS 574B024-036
REQD CLEARANCES FOR OPERATION AND SERVICING. in. (mm)
Evaporator coil access side ..................36(914)
Power entry side (except for NEC requirements) .........36(914)
Unit top ..........................48(1219)
Side opposite ducts .....................36(914)
Duct panel ........................12(304.8)*
*Minimum distances: If unit is placed less than 12 in. (304.8 mm) from wall
system, then the system performance may be compromised.
REQD CLEARANCES TO COMBUSTIBLE MATL. in. (mm)
Top of unit .........................14(355.6)
Duct side of unit .......................2(50.8)
Side opposite ducts .....................14(355.6)
Bottom of unit .......................0.50 (12.7)
Flue panel .........................36(914.4)
NEC REQD CLEARANCES. in. (mm)
Between units, power entry side ..............42(1066.8)
Unit and ungrounded surfaces, power entry side .........36(914)
Unit and block or concrete walls and other grounded
surfaces,
control box side
.................
42
(1066.8)
LEGEND
CG - Center of Gravity
COND - Condenser
EVAP - Evaporator
NEC - National Electrical Code
REQ'D - Required
Note: Dimensions are in in. (mm)
UNIT
ELECTRICAL
CHARACTERISTICS
UNIT WEIGHT
UNIT HEIGHT
IN. [MM]
A
CENTER OF GRAVITY
IN. [MM]
lb. kg. X Y Z
574B024040 208/230-1-60 350 159 39.02 [991.1] 20 [508] 19.3 [489] 17.6 [447]
574B030040/060 208/230-1-60
574B036060/090
208/230-1-60
208/230-3-60
388 176 41.02 [1041.9] 20 [508] 14 [355.6] 13 [330.2]