Bryant 569J Fan User Manual


 
7
Table 2A — Physical Data — 569J*12-14D/E Units — 60 Hz English
UNIT SIZE 569J *12D/E *14D/E
NOMINAL CAP ACITY (tons) 10 12.5
OPERATING WEIGHTS (lb)
NOVATIONCoil (Al Tube) 499 505
Round Tube/Plate Fin C oil (Cu/Al) 516 654
REFRIGERANT TYPE
R-410A
NOVA TION Operating Charge A/B, Typical ( lb)
7.4 / 7.3 10.8 / 10.9
NOVA TION Shipping Charge A/B (lb) 3.0 / 3.0 3.5 / 3.5
RTPF Operating Charge A/B, Typical (l b)
11.0 / 11.0 23.0/23.0
RTPF Shipping Charge A/B (lb) 8.0 / 8.0 17.0/17.0
COMPRESSOR
Qty ...Type 2...Scroll 2...Scroll
Oil Charge A/B (oz) 42 60
CONDENSER FANS
Qty ...Rpm 2...1100
Motor Hp
1
/
4
Diameter 22
Nominal Airflow (Cfm Total) 6000
Watts (Total) 610
RTPF CONDENSER COIL
Material (Tube/Fin) Cu / Al
Coil Type
3
/
8
--- in R TP F
Rows/Fins per inch (FPI) 2/17 3/17
Face Area (sq ft total) 25.0 31.8
NOVATION CONDENSER COIL
Material (Tube/Fin) Al / Al
Coil Type Novation
Rows/Fins per inch (FPI) 1/17
Face Area (sq ft total) 25.0 31.8
CONTROLS
Pressurestat Settings (psig)
High Cutout 630 ± 10
Cut-in 505 ± 20
Low Cutout 54 ± 3
Cut-in 117 ± 5
PIPING CONNECTIONS (in. ODS)
Qty...Suction A/B 1...1
1
/
8
/ 1...1
1
/
8
1...1
3
/
8
/ 1...1
3
/
8
Qty...Liquid A/B 1...
3
/
8
/ 1...
3
/
8
1...
1
/
2
/ 1...
1
/
2
LEGEND
RTPF Round Tube/Plate Fin
ODS Outside Diameter Sweat (socket)
Unit is factory-supplied with partial charge only .
Typical operating charge with 25 ft of interconnecting piping.