47
TROUBLESHOOTING (cont)
PROBLEM SOLUTION
COMPRESSOR CYCLES ON LOW-PRESSURE SWITCH
Indoor-Air F an Running
1. Liquid line solenoid valve(s) fails to open. 1. Check liquid line solenoid valve(s ) for proper operatio n. Replac e if neces sary .
2. Filter drier plugged. 2. Replace filter drier.
3. Expansion valve power head defective. 3. Replace power head.
4. Low refrigerant charge. 4. Add charge. Check low-pressure switch setting.
Airflow Restricted
1. Coil iced up. 1. Check refrigerant charge.
2. Coil dirty. 2. Clean coil fins.
3. Air filters dirty. 3. Clean or replace filters.
4. Dampers closed. 4. Check damper operation and position.
Indoor-Air F an Stopped
1. Electrical connections loose. 1. Tighten all connections.
2. Fan relay defective. 2. Replace relay.
3. Motor overload open. 3. Power supply.
4. Motor defective. 4. Replace motor.
5. Fanbeltbrokenorslipping. 5. Replaceortightenbelt.
COMP RESSOR RUN NING BUT COO L I N G I N S UFF I CI EN T
Suction Pressure Low
1. Refrigerant charge low. 1. Ad d refrigerant.
2. Head pressure low. 2. Check refrigerant charge. Check outdoor-air fan thermostat settings.
3. Air filters dirty. 3. Clean or replace filters.
4. Expansion valve power head defective. 4. Replace power head.
5. Indoor coil partially iced. 5. Check low-pressure setting.
6. Indoor airflow restricted. 6. Remove obstruction.
Suction Pressure High
1. Heat load excessive. 1. Check for open doors or w indows in vicinity of fan coil.
UNIT OPERATES TOO LON G OR CONTINUOUSLY
1. Low refrigerant charge. 1. Add refrigerant.
2. Control contacts fused. 2. Replace control.
3. Air in system. 3. Purge and evacuate system .
4. Partially plugged expansion valve or filter drier. 4. Clean or replace.
SYSTEM IS NOISY
1. Piping vibration. 1. Support piping as required.
2. Compressor noisy. 2. Replace compressor if bearings are worn.
COMPRESSOR LOSES OIL
1. Leak in system. 1. Repair leak.
2. Crankcase heaters not energized during shutdown. 2. Check wiring and relays. Check heater and replace if defective.
3. Improper interconnecting piping design. 3. Check piping for oil return. Replace if necessary.
FROSTED SUCTION LINE
Expansion valve admitting excess refrigerant. Adjust expansion valve.
HOT LIQUID LINE
1. Shortage of refrigerant due to leak. 1. Repair leak and recharge.
2. Expansion valve opens too wide. 2. Adjust expansion valve.
FROSTEDLIQUIDLINE
1. Restricted filter drier. 1. Remove restriction or replace.
2. Liquid line solenoid valve partially closed. 2. Replace valve.
569J