Bryant 551C Fan User Manual


 
24
C06131
Fig. 19 --- Outdoor--Air Damper With Hood Attached
C06132
Fig. 20 --- Outdoor--Air Damper Position Setting
ECONOMI$ER IV
CONTROLLER
OUTSIDE AIR
TEMPERATURE SENSOR
LOW AMBIENT
SENSOR
A
CTUATOR
WIRING
HARNESS
C06021
Fig. 21 --- EconoMi$er IV Component Locations
Optional EconoMi$er
IV
See Fig. 21 for EconoMi$er IV component locations.
NOTE: These instructions are for installing the optional
EconoMi$er IV only. Refer to the accessory EconoMi$er IV
installation instructions when field installing an E c onoMi$er IV
accessory.
1. To remove the existing unit filter access panel, raise the
panel and swing the bottom outward. The panel is now
disengaged from the track and can be removed. (See
Fig. 22.)
2. The box with the economizer hood components is shipped
in the compartment behind the economizer. The
EconoMi$er IV controller is mounted on top of the
EconoMi$er IV. To remove the component box from its
shipping position, remove the screw holding the hood box
bracket to the top of the economizer. Slide the hood box
out of the unit. (See Fig. 23.)
IMPORTANT: If t he power exhaust accessory is to be installed
on the unit, the hood shipped with the unit will not be used and
must be discarded. Save the aluminum filter for use in the power
exhaust hood assembly.
3. The indoor coil access panel will be used as the top of the
hood. Remove the screws along the sides and bottom of
the indoor coil access panel. ( See Fig. 24.)
4. Swing out indoor coil access panel and insert the hood
sides under the panel (hood top). Use the screws provided
to attach the hood sides to the hood top. Use screws
provided to attach the hood sides to the unit. (See Fig. 25.)
5. Remove the shipping tape holding the economizer
barometric relief damper in place.
6. Insert the hood divider between the hood sides. (See
Fig. 25 and 26.) Secure hood divider with 2 screws on
each hood side. The hood divider is also used as the
bottom filter rack for the aluminum filter.
7. Open the filter clips whi ch are l ocated underneath the
hood top. Insert the aluminum filter into the bottom filter
rack (hood divider). Push the filter i nto position past the
ope n filter clips. Close the filter clips to lock the filter into
place. (See Fi g. 26.)
8. Caulk the ends of the joint between the unit top panel and
the hood top. (See Fig. 24.)
9. Replace the filter access panel.
10. Install all EconoMi$er IV accessories. EconoMi$er IV
wiring is shown in Fig. 27.
Barometric flow capacity is shown in Fig. 28. Outdoor air
leakage is shown in Fig. 29. Return air pressure drop is shown in
Fig. 30.
FILTERACCESS PANEL
OUTDOOR-AIR OPENING AND
INDOOR COILACCESS PANEL
COMPRESSOR
ACCESS PANEL
C06023
Fig. 22 --- Typi cal Access Panel Locations
551B,C