Bryant 551B Fan User Manual


 
37
Table 19—Fan Performance 551B 060, 551C 060 Single-Phase — Vertical Discharge Units; Standard Motor (Belt Drive)*
A
I
R
F
L
O
W
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
C
F
M
0.2 0.4 0.6 0.8 1.0
C
F
M
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1500 790 0.40 353 897 0.53 471 991 0.68 600 1075 0.83 739 1152 1.00 888
1600 828 0.46 412 931 0.60 536 1022 0.75 670 1104 0.92 813 1180 1.09 966
1700 866 0.54 478 966 0.68 608 1054 0.84 747 1134 1.01 895 1208 1.19 1053
1800 905 0.62 551 1001 0.77 687 1087 0.94 832 1165 1.11 985 1238 1.29 1148
1900 944 0.71 633 1037 0.87 774 1120 1.04 925 1197 1.22 1084
2000 983 0.81 723 1073 0.98 870 1154 1.16 1026
2100 1023 0.92 821 1110 1.10 975 1189 1.28 1137
2200 1063 1.05 929 1147 1.23 1089
2300 1104 1.18 1046
2400
2500
A
I
R
F
L
O
W
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
C
F
M
1.2 1.4 1.6 1.8 2.0
C
F
M
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1500 1224 1.18 1045
1600 1250 1.27 1128
1700
1800
1900
2000
2100
2200
2300
2400
2500
NOTES:
1. Bold cells indicate field-supplied drive is requi red.
2. Maximum continuous bhp is 1.30.
3. See general fan performance notes.
LEGEND
Bhp Brake Horsepower
Watts — Input Watts to Motor
*Motor drive ran ge: 1035 to 1460 rpm. All other rpms require field-supplied
drive.
551B,C