—38—
DETAILED COOLING CAPACITIES* Continued
NOTE: When the required data falls between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
* Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard 210/240-94. If additional tubing length and/or
indoor unit is located above outdoor unit, a slight variation in capacity may occur.
†Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
‡ Sensible capacities shown are based on 80°F (27°C) entering air at the indoor coil. For sensible capacities at other than 80°F (27°C), deduct 835 Btuh
(245 kW) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80°F (27°C), or add 835 Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil air
per degree above 80°F (27°C). When the required data falls between the published data, interpolation may be performed.
** Total system kW is total of indoor and outdoor unit kilowatts.
†† At TVA rating indoor condition (75°F edb/63°F ewb). All other indoor air temperatures are at 80°F edb.
EVAP
AIR
CONDENSER ENTERING AIR TEMPERATURES °F
75 85 95 105 115 125
CFM EWB
Capacity
MBtuh†
Total
Sys
kW**
Capacity
MBtuh†
Total
Sys
kW**
Capacity
MBtuh†
Total
Sys
kW**
Capacity
MBtuh†
Total
Sys
kW**
Capacity
MBtuh†
Total
Sys
kW**
Capacity
MBtuh†
Total
Sys
kW**Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡
550A060-H Outdoor Section With CD5PX060 Indoor Section
1750
57 57.89 57.89 4.31 55.67 55.67 4.76 53.35 53.35 5.27 50.80 50.80 5.83 47.87 47.87 6.43 44.52 44.52 7.08
62 59.84 53.84 4.33 57.09 52.53 4.78 54.23 51.17 5.28 51.12 49.67 5.84 47.85 47.85 6.43 44.51 44.51 7.08
67 65.37 45.55 4.39 62.27 44.22 4.84 59.00 42.86 5.34 55.44 41.38 5.89 51.48 39.77 6.47 47.02 37.98 7.11
72 71.38 37.24 4.45 67.95 35.91 4.91 64.32 34.50 5.41 60.36 33.01 5.96 55.94 31.39 6.53 50.98 29.58 7.15
2000
57 60.22 60.22 4.42 57.88 57.88 4.89 55.28 55.28 5.39 52.49 52.49 5.95 49.40 49.40 6.55 45.73 45.73 7.19
62 61.19 57.67 4.44 58.34 56.29 4.89 55.34 54.77 5.39 52.48 52.48 5.95 49.40 49.40 6.55 45.71 45.71 7.19
67 66.60 48.31 4.49 63.37 46.97 4.96 59.86 45.53 5.45 56.10 44.02 5.99 52.03 42.39 6.58 47.43 40.59 7.21
72 72.67 38.92 4.56 69.11 37.58 5.02 65.22 36.14 5.52 61.05 34.63 6.06 56.50 32.98 6.63 51.36 31.14 7.25
2250
57 62.16 62.16 4.54 59.57 59.57 5.00 56.86 56.86 5.50 53.93 53.93 6.06 50.56 50.56 6.65 46.69 46.69 7.29
62 62.34 61.20 4.54 59.51 59.51 5.00 56.85 56.85 5.50 53.92 53.92 6.06 50.55 50.55 6.65 46.69 46.69 7.29
67 67.52 50.93 4.60 64.07 49.53 5.06 60.43 48.08 5.55 56.59 46.55 6.09 52.42 44.91 6.67 47.72 43.08 7.31
72 73.65 40.55 4.67 69.86 39.16 5.13 65.83 37.69 5.62 61.56 36.15 6.16 56.87 34.48 6.73 51.61 32.64 7.35
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section Size
Cooling
Indoor
Section Size
Cooling
Capacity Power Capacity Power
CC5A/CD5AA 060 0.95 0.98 CK5A/CK5BT 060 0.97 0.96
CC5A/CD5AW 060 0.98 1.00 CK5A/CK5BX 060 0.99 0.96
CD5PX 060 1.00 1.00 CK5PA 060 0.97 0.96
CE3AA 060 0.98 0.99 CK5PT 060 0.97 0.96
CK3BA 060 0.98 0.99 CK5PX 060 0.99 0.96
CK5A/CK5BA 060 0.98 0.99
COILS + 315(A,J)AV066155 VARIABLE SPEED FURNACE
CK5A/CK5BT 060 0.98 0.99 CC5A/CD5AA 060 0.95 0.95
CK5A/CK5BX 060 1.00 0.99 CD5PX 060 0.98 0.95
CK5PA 060 0.98 0.99 CE3AA 060 0.98 0.95
CK5PT 060 0.98 0.99 CK3BA 060 0.97 0.95
CK5PX 060 1.00 0.99 CK5A/CK5BA 060 0.97 0.95
F(A,B)4BN(F,B,C) 060 0.98 1.01 CK5A/CK5BT 060 0.97 0.95
FB4BNB 070 1.00 1.00 CK5A/CK5BX 060 0.99 0.95
FC4CN(F,B) 060 0.98 1.01 CK5PA 060 0.97 0.95
FC4CNB 070 1.00 1.00 CK5PT 060 0.97 0.95
FE4ANB 006 1.00 0.94 CK5PX 060 0.99 0.95
FG3AAA 060 0.97 0.99
COILS + 355MAV060080 VARIABLE SPEED FURNACE
FK4DNB 006 1.00 0.94 CK3BA 060 0.97 1.01
FV4BNB 006 1.00 0.94 CK5A/CK5BA 060 0.97 1.01
FX4BNB 060 1.00 1.00 CK5A/CK5BT 060 0.97 1.01
COILS + 315(A,J)AV060110 VARIABLE SPEED FURNACE
CK5PA 060 0.97 1.01
CC5A/CD5AA 060 0.95 0.98 CK5PT 060 0.97 1.01
CD5PX 060 0.98 0.98
COILS + 355MAV060100 VARIABLE SPEED FURNACE
CE3AA 060 0.98 0.98 CK3BA 060 0.97 1.00
CK3BA 060 0.97 0.97 CK5A/CK5BA 060 0.97 0.99
CK5A/CK5BA 060 0.97 0.97 CK5A/CK5BT 060 0.97 0.99
CK5A/CK5BT 060 0.97 0.97 CK5PA 060 0.97 0.99
CK5A/CK5BX 060 0.99 0.97 CK5PT 060 0.97 0.99
CK5PA 060 0.97 0.97
COILS + 355MAV060120 VARIABLE SPEED FURNACE
CK5PT 060 0.97 0.97 CC5A/CD5AA 060 0.95 0.99
CK5PX 060 0.99 0.97 CK3BA 060 0.97 0.99
COILS + 315(A,J)AV066135 VARIABLE SPEED FURNACE
CK5A/CK5BA 060 0.97 0.99
CC5A/CD5AA 060 0.95 0.96 CK5A/CK5BT 060 0.97 0.99
CD5PX 060 0.98 0.96 CK5A/CK5BX 060 0.99 0.99
CE3AA 060 0.98 0.96 CK5PA 060 0.97 0.99
CK3BA 060 0.97 0.96 CK5PT 060 0.97 0.99
CK5A/CK5BA 060 0.97 0.96 CK5PX 060 0.99 0.99