Bryant 548F Heat Pump User Manual


 
26
PERFORMANCE DATA
COOLING CAPACITIES
548F036 (3 TONS)
Temp (F)
Outdoor
Entering Air
(Edb)
Indoor Entering Air Cfm/BF
900/0.10 1200/0.15 1500/0.21
Indoor Entering Air Ewb (F)
72 67 62 72 67 62 72 67 62
75
TC
42.4 39.9 36.5 43.0 41.2 38.7 45.1 42.8 40.3
SHC
16.7 22.0 26.8 17.5 24.2 30.9 19.3 26.9 34.1
kW
2.77 2.71 2.62 2.78 2.74 2.68 2.85 2.79 2.73
85
TC
41.5 38.4 34.8 43.3 40.4 37.0 44.0 41.7 38.7
SHC
16.6 21.6 26.2 18.2 24.6 30.3 19.3 27.2 33.7
kW
3.01 2.92 2.80 3.07 2.98 2.88 3.09 3.03 2.94
95
TC
40.0 36.3 33.0 42.3 38.5 35.2 43.4 40.0 36.7
SHC
16.2 20.9 25.7 18.2 24.2 29.8 19.7 27.2 32.7
kW
3.24 3.10 2.99 3.32 3.19 3.07 3.36 3.24 3.13
105
TC
38.4 34.7 31.0 40.0 36.7 33.1 41.2 37.7 35.2
SHC
15.7 20.5 24.8 17.5 23.9 28.8 19.3 26.6 31.7
kW
3.47 3.32 3.16 3.53 3.41 3.26 3.58 3.44 3.35
115
TC
36.1 32.5 28.9 38.1 34.3 31.1 39.3 35.5 33.2
SHC
15.1 19.8 23.9 17.2 23.2 27.8 19.1 26.2 30.2
kW
3.66 3.50 3.32 3.76 3.59 3.44 3.81 3.65 3.54
125
TC
34.2 30.5 26.8 35.9 32.0 29.3 36.8 33.0 31.3
SHC
14.6 19.2 22.9 16.7 22.6 26.3 18.5 25.5 28.4
kW
3.88 3.68 3.49 3.97 3.77 3.62 4.02 3.83 3.74
548F048 (4 TONS)
Temp (F)
Outdoor
Entering Air
(Edb)
Indoor Entering Air Cfm/BF
1200/0.11 1600/0.15 2000/0.22
Indoor Entering Air Ewb (F)
72 67 62 72 67 62 72 67 62
75
TC
55.5 51.9 47.4 56.9 54.6 50.3 59.3 56.5 52.1
SHC
24.5 31.2 37.4 26.0 35.2 43.4 28.4 39.0 47.6
kW
3.80 3.70 3.55 3.84 3.79 3.66 3.93 3.86 3.71
85
TC
53.4 49.7 45.3 56.3 52.6 47.8 57.5 54.1 49.8
SHC
23.8 30.4 36.7 26.3 34.9 42.6 28.3 38.6 46.9
kW
4.10 3.99 3.84 4.23 4.11 3.94 4.27 4.16 4.01
95
TC
52.0 47.4 43.0 53.7 49.9 45.5 54.5 51.6 47.4
SHC
23.4 29.6 35.8 25.5 33.9 41.6 27.3 38.2 45.2
kW
4.47 4.28 4.11 4.53 4.39 4.23 4.56 4.48 4.29
105
TC
49.3 45.0 40.6 51.8 47.2 43.0 52.6 48.7 45.4
SHC
22.5 28.8 34.7 25.3 33.0 40.3 27.1 37.1 43.3
kW
4.77 4.59 4.39 4.90 4.68 4.52 4.92 4.76 4.63
115
TC
46.6 42.4 38.0 48.8 44.6 40.6 50.2 45.8 43.2
SHC
21.7 27.9 33.6 24.3 32.4 38.7 26.8 36.1 41.2
kW
5.08 4.90 4.66 5.21 5.01 4.81 5.29 5.06 4.96
125
TC
44.0 39.6 35.4 45.6 41.6 38.3 47.0 42.9 40.9
SHC
20.9 26.9 32.4 23.3 31.6 36.5 25.9 35.6 39.0
kW
5.45 5.21 4.96 5.51 5.34 5.14 5.60 5.41 5.30
548F060 (5 TONS)
Temp (F)
Outdoor
Entering Air
(Edb)
Indoor Entering Air Cfm/BF
1500/0.05 2000/0.08 2500/0.14
Indoor Entering Air Ewb (F)
72 67 62 72 67 62 72 67 62
75
TC
69.3 64.5 59.3 70.8 67.9 62.8 72.9 69.3 65.4
SHC
30.9 39.2 47.4 33.1 44.9 55.4 35.8 49.4 61.4
kW
4.28 4.15 4.03 4.32 4.25 4.12 4.38 4.29 4.19
85
TC
67.7 62.4 56.8 69.1 65.7 60.2 71.1 67.7 63.2
SHC
30.4 38.6 46.5 32.8 44.6 54.4 35.8 50.0 59.8
kW
4.76 4.61 4.49 4.79 4.72 4.56 4.86 4.78 4.65
95
TC
65.2 59.8 54.4 67.7 62.9 57.6 69.1 64.8 60.7
SHC
29.6 37.6 45.5 32.8 43.6 53.2 35.6 49.3 57.7
kW
5.27 5.10 4.97 5.35 5.20 5.07 5.39 5.27 5.14
105
TC
62.3 57.2 51.8 65.1 59.6 54.9 66.8 61.7 58.3
SHC
28.6 33.8 44.4 32.1 42.6 51.6 35.4 48.2 55.5
kW
5.79 5.66 5.50 5.90 5.73 5.61 5.97 5.79 5.68
115
TC
59.7 54.2 49.0 61.7 57.0 52.5 63.2 58.4 55.8
SHC
27.6 35.8 43.2 31.1 41.9 49.6 34.3 47.0 53.2
kW
6.37 6.24 6.06 6.47 6.34 6.20 6.53 6.36 6.31
125
TC
56.5 51.0 46.0 58.2 53.5 49.8 59.4 55.1 53.0
SHC
26.8 34.7 41.9 30.0 40.8 47.3 33.0 46.5 50.5
kW
7.03 6.87 6.65 7.07 6.96 6.82 7.13 7.03 6.96
LEGEND
NOTES:
1. Direct interpolation is permissible. Do not
extrapolate.
2. The following formulas may be used:
t
lwb
= Wet-bulb temperature corresponding
to enthalpy of air leaving indoor coil
(h
lwb
)
Where: h
ewb
= Enthalpy of air entering evap-
orator coil
3. The SHC is based on 80 F edb temperature
of air entering indoor coil.
Below 80 F edb, subtract (corr factor x cfm)
from SHC.
Above 80 F edb, add (corr factor x cfm) to
SHC.
Interpolation is permissible.
Correction Factor = 1.10 x (1 BF) x
(edb 80).
BF
Bypass Factor
Edb
Entering Dry-Bulb
Ewb
Entering Wet-Bulb
kW
Compressor Motor Power Input
Ldb
Leaving Dry-Bulb
Lwb
Leaving Wet-Bulb
SHC
Sensible Heat Capacity
(1000 Btuh) Gross
TC
Total Capacity (1000 Btuh) Gross
t
ldb
=t
edb
sensible capacity (Btuh)
1.10 x cfm
h
lwb
= h
ewb
total capacity (Btuh)
4.5 x cfm
BYPASS
FACTOR
(BF)
ENTERING AIR
DRY-BULB TEMP (F)
79 78 77 76 75
under
75
81 82 83 84 85
over
85
Correction Factor
.05
1.04 2.07 3.11 4.14 5.18 Use
formula
shown
below.
.10
.981.962.943.924.90
.20
.871.742.623.494.36
.30
.761.532.293.053.82
50TFQ004-012
548F036-120