GUIDE SPECIFICATIONS — 548F AND 549B036-120 UNITS (cont)
15. Compressor Cycle Delay:
Unit shall be prevented from restarting for minimum
of 5 min. after shutdown.
*16. Thru-the-Bottom Utility Connectors:
Kit shall provide connectors to permit electrical con-
nections to be brought to the unit through the
basepan.
*17. Fan/Filter Status Switch:
Provides status of indoor (evaporator) fan (ON/OFF)
or filter (CLEAN/DIRTY). Status shall be displayed
over communication bus when used with direct
digital controls or with an indicator light at the
thermostat.
*18. Solid-State Enthalpy Control:
a. For use with Durablade economizer package only.
b. Capable of sensing outdoor-air enthalpy content
(temperature and humidity) and controlling econ-
omizer cut-in point to have minimum heat content
air passing over the indoor coil for most efficient
system operation.
*19. Differential Enthalpy Sensor:
a. For use with Durablade economizer only.
b. Capable of comparing enthalpy content (tempera-
ture and humidity) of outdoor and indoor air and
controlling economizer cut-in point at the most
economical level.
*20. EconoMi$er with Power Exhaust:
Package shall provide control of internal building
pressure. The two-stage system shall exhaust up to
100% of return air (vertical only).
*21. Two-Stage Power Exhaust Accessory for
EconoMi$er:
Power exhaust shall be used in conjunction with
EconoMi$er to provide system exhaust of up to
100% of return air. The power exhaust is a
field-installed accessory (vertical and horizontal
applications).
The individual fans are energized through the end
switches located in the actuator, which will open as
the outdoor-air damper opens. These end switches
are factory set for 30 and 70% of outdoor-air, and
can be set to meet specific job requirements.
*22. Outdoor Air Enthalpy Sensor:
The outdoor air enthalpy sensor shall be used with
the EconoMi$er device to provide single enthalpy
control. When used in conjunction with a return air
enthalpy sensor, the EconoMi$er device will provide
differential enthalpy control. The sensor allows the
EconoMi$er controller to determine if outside air is
suitable for free cooling.
*23. Return Air Enthalpy Sensor:
The return air enthalpy sensor shall be used with the
EconoMi$er device. When used in conjunction with
an outdoor air enthalpy sensor, the EconoMi$er
device will provide differential enthalpy control.
*24. Return Air Temperature Sensor:
The return air temperature sensor shall be used with
the EconoMi$er device. When used in conjunction
with the standard outdoor air temperature sensor,
the EconoMi$er device will provide differential tem-
perature control.
*25. Power Exhaust Auxiliary Transformer:
Field-installed 460v to 230v transformer to provide
power to the 230v power exhaust when attached to a
460v rooftop unit.
*26. Ultra-Violet Germicidal Lamps:
Ultra-violet germicidal lamps are designed to elimi-
nate odor causing mold and fungus that may develop
in the wet area of the evaporator section of the unit.
The high output, low temperature germicidal lamps
are field installed in the evaporator section of the
unit, aimed at the evaporator coil and condensate
pan. The short wavelength ultra-violet light inhibits
and kills mold, fungus and microbial growth. The
lamps have an output rating at 45 F in 400 fpm air-
flow of 120 microwatts/cm
2
at 1 meter.
*27. Hinged Panel Option (549B only):
Hinged panel option provides hinged access panels
for the filter, compressor, evaporator fan, and control
box areas. Filter hinged panels permit tool-less entry
for changing filters. Each hinged panel is perma-
nently attached to the rooftop unit.
28. Emergency Heat Control Package:
When mechanical heating is locked out, auxiliary
heat shall be activated when necessary.
29. Alternate Motors and/or Drives 548F036-060, 090,
120):
Alternate motors and drives shall be factory-installed
to provide additional performance range.
30. High-Static Motor(s) and Drive(s) (548F036-120):
High-static motor(s) and drive(s) shall be factory-
installed to provide and additional performance
range.