Bryant 542J Air Conditioner User Manual


 
3
SERIAL
MODEL
Compressors (Factory Charged) Refrigerant/System
Qty Volts AC PH Hz RLA LRA lbs kg R
Test Pressure Gage
Hi PSI ( kPa)
SERIAL
MODEL
1
2
Fan Motors Qty PH Hz FLA HP KWVolts AC
Power
Supply
Max
Volts
Min
VoltsPH MCA * MOCP *HzVolts AC
=
Min Circuit Amps
*MOCP
=
Max Over Current Protective Device Amps
*MCA (Fuse or HACR Bkr.)
Test with External Static
in H
2
0
kPa NOT Suitable for Outdoor Use
Designed in U.S.A.
Assembled in Mexico
Part Number/Rev
Charge System per Installation Instructions
99NA504644/2.0
BRYANT
5
1
2
2
6
7
A
8
0
10
4
3
J
4
E
5
1
6
0
9
0
11
A
12
1
13
0
14
A
15
A
16
A
17
Model Number
Position of Digit
524JE16A000A10AAA
C11004
Fig. 2 -- Example of Nameplate with Model Number
Table 1 – Electrical Data, Standard Motors
UNIT V --- PH --- Hz
{
VOLTAGE
LIMITS
FAN MOTOR POWER SUPPLY
Hp (kW) FLA
Minimum
Circuit Amps
MOCP
524J*16A
524J
*16H
208/230---3---60 187---253 3.7 (2.76) 10.6 13.3 20
460 --- 3 --- 60 414---506 3.7 (2.76) 4.6 6.0 15
575 --- 3 --- 60 518---632 3.0 (2.24) 3.8 4.8 15
524J*25A
524J*25H
208/230---3---60 187---253 5.0 (3.73) 14.6/12.8 18.3/16.0 30/25
460 --- 3 --- 60 414---506 5.0 (3.73) 6.4 8.0 15
575 --- 3 --- 60 518---632 5.0 (3.73) 5.1 6.4 15
524J*28A
208/230---3---60 187---253 7.5 (5.59) 21.4/19.4 26.9/24.3 45/40
460 --- 3 --- 60 414---506 7.5 (5.59) 9.7 12.1 20
575 --- 3 --- 60 518---632 7.5 (5.59) 7.8 9.8 15
524J*30A
208/230---3---60 187---253 10.0 (7.46) 28.2/26.8 35.3/33.5 60/60
460 --- 3 --- 60 414---506 10.0 (7.46) 13.4 16.8 30
575 --- 3 --- 60 518---632 10.0 (7.46) 10.3 12.9 20
NOTE: See page 5 for table legend and notes
524J