DETAILED COOLING CAPACITIES# CONTINUED
EVAPORATOR AIR
CONDENSER ENTERING AIR TEMPERA TURES °F (°C)
75 (23.9) 85(29.4) 95(35) 105(40.6) 115 (46.1) 125 (51.7)
CFM
EWB
°F(°C)
Capacity MBtuh
Total
Sys.
KW**
Capacity MBtuh
Total
Sys.
KW**
Capacity MBtuh
Total
Sys.
KW**
Capacity MBtuh
Total
Sys.
KW**
Capacity MBtuh
Total
Sys.
KW**
Capacity MBtuh
Total
Sys.
KW**
Total Sens} Total Sens} Total Sens} Total Sens} Total Sens} Total Sens}
123ANA060 Outdoor Section With 60 Indoor Sect ion
1750
72 (22.2) 67.65 35.66 4.15 64.56 34.48 4.58 61.30 33.25 5.06 57.89 31.98 5.58 54.20 30.63 6.15 50.10 29.15 6.77
67 (19.4) 62.07 43.94 4.10 59.24 42.75 4.53 56.25 41.50 5.01 53.12 40.22 5.54 49.74 38.85 6.11 46.03 37.38 6.74
62 (16.7) 57.01 52.17 4.06 54.45 50.95 4.49 51.79 49.66 4.97 49.04 48.27 5.50 46.34 46.34 6.08 43.50 43.50 6.72
57 (13.9) 55.50 55.50 4.04 53.42 53.42 4.48 51.22 51.22 4.96 48.89 48.89 5.50 46.35 46.35 6.08 43.51 43.51 6.72
2000
72 (22.2) 68.69 37.30 4.26 65.46 36.09 4.69 62.07 34.85 5.16 58.54 33.56 5.69 54.71 32.19 6.26 50.48 30.69 6.87
67 (19.4) 63.07 46.60 4.21 60.11 45.38 4.64 57.00 44.12 5.11 53.75 42.82 5.64 50.27 41.45 6.21 46.44 39.94 6.84
62 (16.7) 58.17 55.80 4.16 55.57 54.47 4.59 52.95 52.95 5.07 50.49 50.49 5.61 47.78 47.78 6.19 44.74 44.74 6.82
57 (13.9) 57.57 57.57 4.16 55.35 55.35 4.59 52.99 52.99 5.07 50.50 50.50 5.61 47.78 47.78 6.19 44.74 44.74 6.82
2250
72 (22.2) 69.44 38.83 4.36 66.10 37.62 4.79 62.61 36.36 5.27 58.97 35.06 5.79 55.04 33.67 6.36 50.70 32.16 6.97
67 (19.4) 63.79 49.12 4.31 60.73 47.89 4.74 57.53 46.62 5.21 54.20 45.31 5.74 50.63 43.90 6.31 46.72 42.34 6.93
62 (16.7) 59.18 59.18 4.27 56.90 56.90 4.70 54.41 54.41 5.18 51.77 51.77 5.72 48.91 48.91 6.30 45.70 45.70 6.93
57 (13.9) 59.25 59.25 4.27 56.90 56.90 4.70 54.42 54.42 5.18 51.78 51.78 5.72 48.91 48.91 6.30 45.70 45.70 6.93
COOLING INDOOR
MODEL
CAPACITY POWER FURNACE MODEL
*CAP**6024A** 1.00 1.00
CAP**6021A** 0.98 0.98
CNPH*6024A** 0.97 0.97
CNPV*6024A** 0.99 0.99
CSPH*6012A** 0.98 0.98
FE4ANB006 0.99 0.97
FV4BNB006 0.99 0.97
FX4CN(B,F)060 1.01 1.01
FY4ANB060 0.98 0.98
CAP**6021A** 0.97 0.97 315(A,J)AV060110
CSPH*6012A** 0.97 0.97 315(A,J)AV060110
CAP**6024A** 0.98 0.98 315(A,J)AV066135
CNPH*6024A** 0.97 0.96 315(A,J)AV066135
COOLING INDOOR
MODEL
CAPACITY POWER FURNACE MODEL
CNPV*6024A** 0.97 0.97 315(A,J)AV066135
CSPH*6012A** 0.97 0.95 315(A,J)AV066135
CAP**6024A** 0.98 0.97 315(A,J)AV066155
CNPH*6024A** 0.98 0.97 315(A,J)AV066155
CNPV*6024A** 0.98 0.97 315(A,J)AV066155
CSPH*6012A** 0.97 0.95 315(A,J)AV066155
CNPH*6024A** 0.97 0.97 353AAV048080
CSPH*6012A** 0.97 0.97 353AAV048080
CAP**6021A** 0.97 0.96 353AAV060100
CNPH*6024A** 0.97 0.95 353AAV060100
CSPH*6012A** 0.97 0.96 353AAV060100
CAP**6024A** 0.97 0.96 353AAV060120
COOLING INDOOR
MODEL
CAPACITY POWER FURNACE MODEL
CNPH*6024A** 0.97 0.96 353AAV060120
CNPV*6024A** 0.97 0.96 353AAV060120
CSPH*6012A** 0.97 0.96 353AAV060120
CNPH*6024A** 0.97 0.97 313*AV048090
CSPH*6012A** 0.97 0.97 313*AV048090
CAP**6021A** 0.97 0.97 313* AV060110
CNPH*6024A** 0.97 0.97 313*AV060110
CSPH*6012A** 0.98 0.94 313*AV060110
CAP**6024A** 0.97 0.97 313* AV060135
CNPH*6024A** 0.97 0.97 313*AV060135
CNPV*6024A** 0.97 0.97 313*AV060135
CSPH*6012A** 0.97 0.97 313*AV060135
* Tested combination.
{ Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
} Sensible capacities shown are based on 80_F(27_C) entering air at the indoor coil. For sensible capacities at other than 80_F(27_C), deduct 835 Btuh
(245 kW) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80_F(27_C), or add 835 Btuh (245 kW) per 1000 CFM (480 L/ S ) of indoor coil air per degree above 80_F(27_C).
# Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per AHRI standard 210/ 240--- 94. If a dditional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may
occur.
** System kw is total of indoor and outdo or unit k ilowatts.
{{ At TV A rating ind oor condition (75_F edb/63_F ewb). All other indoor air temperatures are at 80_F edb.
NOTE: When the required data falls between the published data, interp olation may be performed. Extrapolation is not an acceptable practice.
EWB — Entering Wet Bulb
123A