Bradford-White Corp EFR160T120 Water Heater User Manual


 
24
2. Use the proper PVC cement to secure the exhaust vent and air intake terminals provided with the water heater to the
plastic pipes. The distance between the back edge of the exhaust vent terminal and the exterior wall (see Figure 13)
must be 6 inches (12.7 cm) more for the exhaust vent terminal than the air intake terminal. Use the proper cement or
sealant and assembly procedures to secure the vent connector joints between the terminal and the blower outlet.
Provide support brackets for every 3 feet (.9 m) of horizontal vent beyond the intake terminal.
Figure 13. Typical Horizontal Direct Vent System
Vertical Installation:
Vertical venting system must be supported every 5 feet (1.5 m) of vertical run and every 3 feet (.9 m) of horizontal run of vent
pipe length.
CAUTION
Failure to properly support the vent piping with hangers and clamps may result in damage to the
water heater or venting system.
Stress levels in the pipe and fittings can be significantly increased by improper installation. If rigid pipe clamps are used to
hold the pipe in place, or if the pipe cannot move freely through a wall penetration, the pipe may be directly stressed, or high
thermal stresses may be formed when the pipe heats up and expands. Install accordingly to minimize such stresses.
Follow the following procedure to vent through the roof:
1. Cut the necessary holes through the roof and ceiling.
2. Install the exhaust vent and air intake plastic pipes as shown in Figure 14. Make sure that the installation meets the
local codes and/or The National Fuel Gas Code ANSI Z223.1 (Latest Edition) or CGA/CAN B149 Installation Code
(Latest Edition).