Beckett 7559 Burner User Manual


 
2
Table 1 - Model Guide
Beckett
GeniSys
24V Control
Part No.
Lockout
Time
Valve-on
delay
time
1
Motor-
off
delay
time
1
7559A 0000
1
15 sec 0 sec 0 sec
7559P 1530
1
15 sec 15 sec 30 sec
7559P 152M
1
15 sec 15 sec 2 min
7559P 158M
1
15 sec 15 sec 8 min
1 Valve-on delay and motor-off delay timings on all models are
programmable with the Beckett Contractor Tool. Other factory
set timings are available. Contact Beckett for alternate
timings.
Features
Welded Relay Protection
Limited Relight
Valve-On Delay / Motor-Off Delay (Field
programmable with Beckett’s Contractor Tool)
15 Second Lockout Time
Interrupted Ignition
Communication Port
Lockout Alarm Output
Fused Protection
Specifications
Electrical Ratings
Inputs:
Voltage: 24 Vdc nominal (21.6 to 30 Vdc)
Current: 220 mA nominal (230 mA max at 30 Vdc)*
Enable Load: 22mA at 24 Vdc
Outputs:
Motor:
24 Vdc, 10 full load amps (FLA), 50 locked rotor
amps (LRA)
Igniter: 24 Vdc, 3 A
Solenoid Valve: 24 Vdc, 1 A
Lockout Alarm: 24 Vdc, 1A
Do Not Use This Control
in an Application that
is Not Within the Ratings Listed in This
Section. Improper Control Operation May
Result.
Do Not Use This Control
Above 5.5 GPH
CAUTION
A low or erratic power supply could
result in impaired burner operation,
severe delayed ignition or an explosion
inside the heat exchanger resulting in a
burn and/or asphyxiation hazard.
Maintain Speci ed
Voltage
Beckett DC Burners require a
continuous supply of 21.6 to 30 volts
DC (at 11 amps for Model ADC or 15
amps for Model SDC), measured at
the burner during operation.
Consult other DC burner
manufacturers’ speci cations for the
correct voltage range.
Special Note: The 7559 Control
shuts the burner down if the input
voltage drops to a sustained level
of 20 volts DC, or below. Operation
resumes at a sustained input
voltage of 21 volts DC, or above.
An automotive or small engine
charging system that is capable of
supplying the required continuous
voltage/amperage is recommended
with certain road equipment, such
as asphalt hot patchers and similar
applications.
This is especially true while
maintaining nominal load temperatures
during idle periods.
y
y
y
y
y
WARNING
CAUTION
Environmental Ratings:
Storage and Operating Ambient Temperature:
-40°F to +160°F (-40°C to +71°C)
Moisture: 5 to 95% RH, condensing
The 7559 control draws
40-55mA in the standby
state. If the red control wire is left powered
without a battery charging system, it can
drain a standard 45 Amp hour automotive
battery in four to six weeks.