BEA 80.0011.02 Door User Manual


 
SIZE:
DRAWN BY:
TITLE: MC-25 WITH RECEIVER, ELECTRIC
STRIKE, PUSHPLATE, LOW ENERGY
AUTOMATIC DOOR APPLICATION
A
100 ENTERPRISE DRIVE
PITTSBURGH, PA 15275
PHONE: (412) 249-4100
FAX: (412) 249-4101
EMAIL: www.beasensors.com
REV BY:
KJG JEG
80.0011.02
SCALE: DATE:
NONE 24 APR 2005
PART NO:
SHEET
1 OF 1
NOTE: 1) JUMPERS ARE PLACED ON J1 PINS 1&2, J2 PINS 4&5 FOR DRY CONTACTS ON RELAY OUTPUT #1.
2) PUSH PLATE, MOTION SENSOR, CARD READER MUST BE DRY CONTACT.
3) TRANSFORMER AND BRIDGE RECTIFIER VOLT/ AMPERE RATING IS DETERMINED BY CURRENT DRAW OF
ELECTRIC STRIKE.
GRAY
6
5
4
3
2
1
MC-25
RELAY 1
RELAY 2
RED COMMON
COM
N/O
BLACK
RED
GREEN
WHITE
POWER 24 VAC
POWER 24 VAC
N / O
COMMON
AUTOMATIC
DOOR CONTROL
ACT
-+
DC-ELECTRIC
STRIKE
BRIDGE
RECTIFIER
~~
+
-
IF AFTER TROUBLESHOOTING A PROBLEM, A SATISFACTORY SOLUTION CANNOT BE ACHIEVED, PLEASE CALL B.E.A., INC.
FOR FURTHER ASSISTANCE DURING EASTERN STANDARD TIME AT 1-800-523-2462 FROM 8AM - 5PM. FOR AFTER-HOURS,
CALL EAST COAST: 1-866-836-1863 OR 1-800-407-4545 / MID-WEST: 1-888-308-8843 / WEST COAST: 1-888-419-2564. DO NOT
LEAVE ANY PROBLEM UNRESOLVED. IF YOU MUST WAIT FOR THE FOLLOWING WORKDAY TO CALL B.E.A., LEAVE THE
DOOR INOPERABLE UNTIL SATISFACTORY REPAIRS CAN BE MADE. NEVER SACRIFICE THE SAFE OPERATION OF THE
AUTOMATIC DOOR OR GATE FOR AN INCOMPLETE SOLUTION.WEB: WWW.BEASENSORS.COM
24 V
TRANSFORMER