Bard WA121 Air Conditioner User Manual


 
Manual 2100-234I
Page 6 of 17
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be checked
for external signs of shipping damage. If damage is
found, the receiving party must contact the last carrier
immediately, preferably in writing, requesting inspection
by the carrier’s agent.
GENERAL
The equipment covered in this manual is to be installed
by trained, experienced service and installation
technicians.
The refrigerant system is completely assembled and
charged. All internal wiring is complete.
The unit is designed for use with or without duct work.
Flanges are provided for attaching the supply and return
air ducts.
These instructions explain the recommended method to
install the air cooled self-contained unit and the electrical
wiring connections to the unit.
These instructions and any instructions packaged with
any separate equipment required to make up the entire air
conditioning system should be carefully read before
beginning the installation. Note particularly “Starting
Procedure” and any tags and/or labels attached to the
equipment.
While these instructions are intended as a general
recommended guide, they do not supersede any national
and/or local codes in any way. Authorities having
jurisdiction should be consulted before the installation is
made. See Page 3 for information on codes and
standards.
Size of unit for a proposed installation should be based
on heat loss calculation made according to methods of
Air Conditioning Contractors of America (ACCA). The
air duct should be installed in accordance with the
Standards of the National Fire Protection Association for
the Installation of Air Conditioning and Ventilating
Systems of Other Than Residence Type, NFPA No. 90A,
and Residence Type Warm Air Heating and Air
Conditioning Systems, NFPA No. 90B. Where local
regulations are at a variance with instructions, installer
should adhere to local codes.
Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.
Based on 75° C copper wire. All wiring must conform to NEC and all local codes.
These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the
National Electrical Code (latest revision), article 310 for power conductor sizing.
CAUTION: When more than one field power conductor circuit is run through one conduit, the conductors
must be derated. Pay special attention to note 8 of table 310 regarding Ampacity Adjustment Factors when
more than 3 conductors are in a raceway.
TABLE 2
ELECTRICAL HEAT SPECIFICATIONS
TIUCRICELGNIS
sledoM
stloVdetaR
dna
esahP
dleiF.oN
rewoP
stiucriC
3
muminiM
tiucriC
yticapmA
1
mumixaM
esuFlanretxE
tiucriCro
rekaerB
2
rewoPdleiF
eziSeriW
2
dnuorG
eziSeriW
00A-121AW
30A
50A
1-802/032
1
1
1
8
02
72
51
02
03
41
21
01
41
21
01
00K-121AW
20K
1-511
1
1
71
52
52
03
01
01
01
01
00G-121AW
20G
30G
1-05-022
1
1
1
7
31
02
51
51
02
41
41
21
41
41
21