ZC Kit – Large Pellet Insert
(99200149)
Page 3 of 8 10/9/06 © Travis Industries, Inc.
Vent Termination Requirements (See the illustration below)
• Must have an approved cap (to prevent water from entering) or a 45° downturn.
• If the termination is located on a windy side of the house, an approved house shield is
recommended to prevent soot from building up on the side of the house.
• Must not be located where it will become plugged by snow or other material.
• Horizontal terminations must protrude 12" from the wall, vertical terminations require 24".
H
G
A
D
F
NOTE: Measure clearances to the nearest edge of the exhaust hood.
A
E
B
C
F
X
A Minimum 4' clearance below or beside any door or window that opens
B Minimum 1' clearance above any door or window that opens
C Minimum 2' clearance from any adjacent building
D Minimum 7' clearance above any grade when adjacent to public walkways
NOTE: Vent may not terminate in covered walkway or breezeway.
E Minimum 2' clearance above any grass, plants, or other combustible materials
F Minimum 3' clearance from any forced air intake of any other appliance
G Minimum 2' clearance below eaves or overhangs
H Minimum 1' clearance horizontally from combustible wall
X Must be a minimum of 2' above the roof