Ariston G.C.N.:47-116-67 (38 kW) Boiler User Manual


 
19
installation
Warning
The exhaust gas ducts must not be in contact with or close
to in ammable material and must not pass through building
structures or walls made of in ammable material.
When replacing an old appliance, the  ue system must be
changed.
Important
Ensure that the  ue is not blocked.
Ensure that the  ue is supported and assembled in accordance
with these instructions.
150 mm
118
* Min slope: 1˚
1˚= 17.5mm per metre
150 mm
* pente
Installation without extension
Installation with extension
Level
Level
Fitting the Coaxial Flue (Ø 60 / 100 Horizontal)
Contents:
1x Silicone O-Ring (60mm)
1x Elbow (90°)
2x Wall Seals (Internal & External)
1x Flue Pipe including Terminal (1 metre - 60/100)
2x Flue Clamps
4x Screws
2x Seals
Once the boiler has been positioned on the wall,  t the rubber
ue seal into the internal  ue turret (see diagram opposite),
Insert the elbow into the socket and rotate to the required
position. note: It is possible to rotate the elbow 360° on its vertical
axis.
Using the  ue clamp, seals and screws supplied (Fig 4) secure the
elbow to the boiler.
The 1 metre horizontal  ue kit (3318073) supplied is suitable for
an exact X dimension of 753mm.
Measure the distance from the face of the external wall to the face
of the  ue elbow (X - Fig 2), this  gure must now be subtracted
from 753mm, you now have the total amount to be cut from the
plain end of the  ue.
Draw a circle around the outer  ue and cut the  ue to the required
length taking care not to cut the inner  ue, next cut the inner
ue ensuring that the length between the inner and outer  ue is
maintained. (Fig 4).
e.g.
X = 555mm
753-555 = 198mm (Length to be cut from the plain end of the
ue).
Once cut to the required length, ensure that the  ue is free from
burrs and reassemble the  ue. If  tting the  ue from inside of
the building attach the outer wall seal to the  ue terminal and
push the  ue through the hole, once the wall seal has passed
through the hole, pull the  ue back until the seal is  ush with the
wall. Alternatively, the  ue can be installed from outside of the
building, the outer seal being  tted last.
Should the  ue require extending, the  ue connections are push
t, however, one  ue bracket should be used to secure each metre
of  ue.
Note: See table for maximum and minimum  ue runs.
slope
Fig. 3
Note: A Plume management kit is available for 60/100
horizontal termination. Instructions for installation are
supplied with the Plume management kit.