Aquacal H/AT120R Heat Pump User Manual


 
12
Typical Installation Clearances
Code Required Clearances:
In addition to the previously stated clearance requirements, follow all applicable local, state, and national
requirements relative to spacing from other objects or equipment.
Placement of Heater
Indoor installations can be problematic, and for that reason are discouraged. However, if no viable alternative
exists, indoor installations may be successfully accomplished provided very exacting criteria is addressed.
Every indoor installation is unique; therefore, there are no specific guidelines for this type of installation. If
considering an indoor installation, you are strongly urged to contact AquaCal Engineering or Technical
departments (800-786-7751) for assistance prior to proceeding.
Outdoor Installation
INSTALLATION
Indoor Installation
Service and Operational Clearances:
To operate correctly, heat pumps require large volumes of air moving over the heat collector. Allow
adequate clearance between the heat pump and walls, fences, shrubs, or other objects. Refer to
recommended clearance drawings below.
Allow five (5) feet of vertical clearance between the top of the heat pump and any roof overhang or other
obstruction. This clearance prevents cold discharge air from recirculating back into the heat pump
(recirculation would reduce the overall performance of the heat pump).
The access panel requires removal during installation and service. Do not place plumbing, or other
items, closer than 30” from the front of the heater.
FRONT-SIDES-REARFRONT-REAR-OVERHEAD
24-
I
NCHES
(
SIDE
)
12-I
NCHES
(R
EAR
)
24-
I
NCHES
(
SIDE
)
30-I
NCHES
(
FRONT
)
RAIN RUN
-
OFF MUST BE
DIRECTED
AWAY FROM
UNIT
.
OVERHANG
WITH
GU
TTE
R
30” M
INIMUM
C
LEARANCE
,
F
RONT
1 F
T
.
MINIMUM
C
LEARANCE
,
R
EAR
5
FT
.
MINIMUM
CLEARANCE
,
O
VERHEAD