18 NetworkAIR Rack Air Removal Unit Installation
To remotely control the Rack Air Removal Unit:
1. Set the second, third, and fourth DIP switches to
give the Rack Air Removal Unit a unique A-Link
address between one and eight, according to the
chart.
2. Plug the APC Environmental Management System into the A-Link “IN” connector.
3. Set the fan speed selector to Remote.
Use the APC Environmental Management System to control the temperature in the rack and to
monitor the Rack Air Removal Unit for any alarms.
1 2 3 4
1=
234
2=
3=
4=
5=
6=
7=
1 234
8=
234111
1
2341
2341
2341
234
1
2341
C
35
5
3
2
6
OFF
32
29.5
kW
38