APC ACF102BLK Fan User Manual


 
Operation
12 NetworkAIR Rack Air Removal Unit Installation
Temperature Override in each Fan Speed Mode
kW mode Exhaust temperature
mode
Remote mode
Temp Override
Enabled
Fan speed will increase
when rack equipment
exhaust temperature
reaches 40.5° C
(105° F)
No Effect Depends on the fan speed
selection of the remote
device. Same as kW or
exhaust temperature mode.
In kW mode the
temperature override
setpoint can be set to
32.2–51.6° C (90–125°
F)
Temp Override
Disabled
No Effect No Effect No Effect
Note
If a Computer Room Air Conditioner fails, the subsequent rise in ambient temperature
can cause the temperature override to activate. Increasing the fan speed can have an
impact on the airflow in the room.