A.O. Smith BFC - 80 Water Heater User Manual


 
Installation
32 Instruction manual BFC
3
is
Appliance with parallel flue gas discharge material
The longest pipe must be used to check the maximum length. In this case, the
chimney pipe is the longest. This is 35 metres. This 35 metres is the sum of pipe
sections 1, 2, 3, 4 and 5. The length of the transition piece can be ignored. The
total number of bends used in the flue gas discharge and air supply is 8. The
bend in the transition piece can be ignored. According to the table, 2.4 metres
per bend must be added. This brings the total pipe length to:
(2.4 x 8) + 35 = 19.2 + 35 = 54.2m.
This is less than the maximum length of 60 metres stated in the table. The
installation therefore fulfils the requirements.