Amcor UCHW-H12CF2 Air Conditioner User Manual


 
3
*
Installation fixture of indoor unit
*
INSTALLATION & REPAIR GUIDE
Split Wall-Mounted air conditioner
Pipelines can be connected in the directions of****
****and*
as indicated in Fig.1. When the pipelines
are connected to the directions of***and*, a groove
for the pipes has to be opened at the proper place on
the base stand.
*Rear outlet
*Left rear outlet
*Left outlet
*Right outlet
*Bottom outlet
Fig.1
1.Installation of wall-mounting plate
Fix the wall-mounting plate firmly on the wall with screws.
Make sure of the leveling of the plate. Slanted wall-mounting
plate might jeopardize the smooth discharge of the condensed
water.
2.Drill holes on the wall
3.Installation of drain pipe
Install the pipelines of the indoor unit in accordance with
the direction of the wall holes. Wrap tightly the drain pipe
and the pipelines with tape. Make sure that the drain pipe
is underneath the pipelines. (Fig.3) (When the drain pipe
passes the room interior, some condensed water might
occur to its surfaces if the humidity is very high).
4.Installation of indoor unit
Pass the connection wires, connecting pipelines and drain
pipe through the wall hole. Hang the indoor unit on the
hooks at the top of the wall-mounting plate so that the
hooks at the bottom of the indoor unit match the hooks of
the wall-mounting plate. (Fig.4)
Fig.2
Fix with a tape
Wall cap
Wall pipe
Interior
Exterior
5-10mm lower
(1/5-2/5")
Wall
Fig.3
Pipelines of indoor unit
Drain pipe
Rear pipe
Bottom hooks
Hook supports
Top hooks
Fig.4
Drill holes at places slightly below the wall-mounting plate,
with hole diameter of 65mm(2-3/5") and the outer edge of
the hole 5-10mm(1/5-2/5") lower (Fig.2) so that the condensed
water can smoothly flow out. Cut the wall penetrating pipe
to proper length according to the thickness of the wall (3-
5mm(1/10-1/5") longer than the wall thickness) and insert
the pipe as indicated in Fig.2.