A SERVICE OF

logo

036-21342-002 Rev. E (0505)
12 Unitary Products Group
ACCESSORIES
Refer to Price Manual for specific model numbers.
TXV Kit - Factory specified and required for proper unit per-
formance.
E4TS030 = 1TV0701
E4TS036 = 1TV0702
E4TS048 = 1TV0703
E4TS060 = 1TV0703
Room Thermostat - Matching 2-Stage cooling thermostats
are available to provide features required for any installation.
See list below:
2ET03700624 - Honeywell Programmable
2ET03700524 - Honeywell Non-Programmable
2EP32U70124 - White Rodgers Programmable
Dehumidification Control - Model 2HU06700124 available
for use in areas where a higher level of humidity control is
required.
Fossil Fuel Relay (Model 2FF02700101) - Required for use
with all furnace applications.
SOUND RATINGS*
* Rated in accordance with ARI 270-95 Standards.
E4TS048
P1XDD20V112
G2FD060S24
1 880 21400 - - 3.30
2 880 43000 23800 7.7 3.34
2 1580 46500 25800 8.0 3.52
G2FD061H24
1 880 22000 - - 3.38
2 880 44000 24400 7.9 3.42
2 1580 47500 26400 8.2 3.60
P1XUD20V112 24
G1UA060S24
1 915 22200 - - 3.34
2 915 44000 25000 7.8 3.36
2 1620 47500 27000 8.1 3.54
G1FA060S24
1 915 22200 - - 3.34
2 915 44000 25000 7.8 3.36
2 1620 47500 27000 8.1 3.54
G2FD060S24
1 915 22200 - - 3.34
2 915 44000 25000 7.8 3.36
2 1620 47500 27000 8.1 3.54
G2FD061H24
1 915 22600 - - 3.40
2 915 45000 25600 8.0 3.44
2 1620 48500 27600 8.3 3.62
E4TS060
P1XDD20V112
G2FD060S24
1 1000 23400 - - 3.38
2 1000 49500 26000 7.5 3.28
2 1800 54000 28400 7.9 3.46
G2FD061H24
1 1000 23400 - - 3.48
2 1000 50500 26600 7.9 3.35
2 1800 55000 29000 8.2 3.52
P1XUD20V112 24
G1UA060S24
1 990 23200 - - 3.34
2 990 49500 26000 7.6 3.34
2 1800 54000 28400 8.0 3.52
G1FA060S24
1 990 23200 - - 3.34
2 990 49500 26000 7.6 3.34
2 1800 54000 28400 8.0 3.52
G2FD060S24
1 990 23200 - - 3.34
2 990 49500 26000 7.6 3.34
2 1800 54000 28400 8.0 3.52
G2FD061H24
1 990 23200 - - 3.42
2 990 50500 26600 8.0 3.40
2 1800 55000 29000 8.3 3.58
1. Heating MBH based on ARI standards of 70° DB entering indoor air, 72% RH outdoor air with 25 feet of interconnecting piping and
no supplemental electric heat operation.
2. Integrated heating capacities include the effect of defrost cycles in the temperature range where they occur.
3. HSPF (Heating Seasonal Performance Factor) is the total heating output during a normal annual usage period for heating divided
by the total electric power input during the same period.
4. COP equals MBH output divided by (total KW input x 3.412).
HEATING CAPACITY - Variable Speed Furnace (Continued)
UNIT
MODEL
VARIABLE SPEED
FURNACE MODEL
WCOIL MODEL
HEATING
STAGE
(# CYL)
RATED
CFM
NET MBH
1,2
HSPF
3
COP
4
@ 47 F
47 OD 17 OD
UNIT MODEL
SOUND RATINGS
(dba)
1 CYLINDER 2 CYLINDER
030 72 73
036 75 78
048 77 79
060 79 81