E6581277c
- 13 -
4.3.4. Memory protection function “prot
The memory protection function protects the selected memory from being overwritten.
When this function is initiated copying data to the memory is prohibited. Reading the memory data is
permitted.
When all the memories are initialized by memory initialization function (clr), the LED indications
are as follows:
in”, “a”, “b”, “c” = “off”, “sup” = “on
This is also the default setting at the time of shipment.
Operating procedure
Key LED indication
Key operation and description
SFT
copycomp
prot
< Selecting a desired function >
Select “prot” (memory protection function) with the [SFT] key.
ENT
prot
in
< Entering the selected function >
After selecting “prot” with the [SFT] key, press the [ENT] key and
in” (selecting inverter memory) appears in the display window.
SFT
inabc
supin
< Selecting a memory to protect its data >
Each time the [SFT] key is pressed, the display changes as follow
in
selecting inverter memory
a
selecting memory A
b
selecting memory B
c
selecting memory C
sup
special parameter selection
(
*
1)
and to “in” again in this order.
ENT
in
off
in
on
< Entering the memory to protect its data >
After selecting “in” (selecting inverter memory, by way of example)
with the [SFT] key, press the [ENT] key and the display shows the
present memory protection status. (When “on” appears on the
display, the selected memory is protected. When “off” appears
on the display, the selected memory is not protected.)
SFT
offon
off
< Protecting the selected memory >
Each time the [SFT] key is pressed, the indication in the display
changes
on
protecting the selected memory (write prohibited)
off canceling protection of the selected memory (write
permitted)
alternately.
ENT
on
prot
< Executing protection of the selected memory >
After selecting “on” (protecting the selected memory, by way of
example) with the [SFT] key, press the [ENT] key. Remote Keypad
starts protecting the selected memory (canceling the protection in
case of “off”) and the indication in the display window returns to
prot”.
- If the [ESC] key is pressed, Remote Keypad returns to previous status (except when executing).
(*1) The Protecting operation of “sup” is different from that provided for other memories and is shown below.
With the same inverter types With different inverter types
(capacity, voltage class) (capacity, voltage class)
sup
Standard
parameters
Special
parameters
sup
Standard
parameters
Special
parameters
on
9
on
9
off
99
off
(
*
2)
––
9”: Protection disabled (write permitted), ”: Write protected (write prohibited)
(*2) In this case, copying operation of parameters from one inverter to another inverter of a different capacity or
a different voltage class.