G8000 Series Installation and Operation Manual
12.3 Electrical Specication
AC Input Rated Capacity 100 kVA (80 kW) 150 kVA (120 kW) 225 kVA (180kW) 300 kVA (240 kW)
Input Voltage 480 V ( +10% to -15% ), 3-Phase 3-Wire
Input Frequency 60 Hz ±5%
Input Power Factor 0.95 – 1.00 Lagging ( at 100% Load )
Current Harmonic Distortion 4% Maximum ( at 100% Load )
Input Capacity Required 107 kVA 154 kVA 232 kVA 309 kVA
Circuit Breaker Rating At 480V
Input
150 A Trip 225 A Trip 350 A Trip 500 A Trip
DC Input Rated Capacity 100 kVA (80 kW) 150 kVA (120 kW) 225 kVA (180 kW) 300 kVA (240 kW)
Voltage Window 288 – 414 V
Recharge Voltage Regulation ± 1.5%
AC Output Rated Capacity 100 kVA (80 kW) 150 kVA (120 kW) 225 kVA (180 kW) 300 kVA (240 kW)
Output Voltage 480/277 V ± 1%, 3-Phase 4-Wire
Output Power Factor 0.8 Lagging
Voltage Distortion 3% with 100% Linear Load / 5% with Non-Linear Load
Transient Voltage Regulation < ± 2%
Transient Settling Time < 50 ms
Crest Factor < 2.0
Output Frequency 60 Hz ± 0.01% ( at Free-running Mode)
Synchronous Window To Utility Line 59 Hz – 61 Hz
Frequency Slew Rate 1 Hz/Sec
Over Load Rating 100%-Continuous / 125% – 10 min. / 150% – 1 min.
WARNING
DO NOT open the front cover.
Electric shock, burns or other personal injuries may occur if untrained
personnel open the front cover.