Basic Hardware and Function
301
10. Troubleshooting
Error messa
e and related information Special Meanin
and countermeasures
Event Info 1 Info 2 Info 3 device
Batt volta
e drop S00F In the power-up initialization, data invalidit
of
RAM (back-up area) has been detected.
If retentive re
isters are used, these validit
are not
uaranteed. (No error down)
Boundar
error Pro
ram
t
pe -
Address
in the
FUN No. The re
ister of index modification is other
than RW, T, C and D. (Error down)
block No. block S064 The re
ister desi
nated b
index modification
has exceeded the allowable ran
e. That is,
out of RW, T, C and D.
(No error down)
Check the value of the index re
ister.
Clock-calendar error S00A The data of built-in calendar LSI is ille
al.
(No error down)
Set the date and time. (T1S onl
)
Duplicate entr
No. Pro
ram
t
pe -
block No.
Address
in the
block
Entr
No. Multiple SUBR instructions which have the
same subroutine number are pro
rammed.
(Error down)
Check the pro
ram.
EEPROM BCC error Ille
al
BCC
S004
S013
BCC error has been detected in the user
pro
ram of the EEPROM. (Error down)
Reload the pro
ram and execute EEPROM
write operation a
ain.
EEPROM warnin
Number
of excess
writin
S007 The number of times of writin
into EEPROM
has exceeded the life (100,000 times). (No
error down)
Replace the unit because the data reliabilit
of the EEPROM will decrease.
I/O bus error Unit No. Data S005
S020
An abnormalit
has been detected in I/O bus
checkin
. (Error down)
Check the expansion cable connection and
I/O module mountin
status.
I/O mismatch Unit No. -
slot No.
Re
ister
No.
S005
S021
The I/O allocation information and the actual
I/O confi
uration are not identical.
(Error down)
Check the I/O allocation and the option card
mountin
status.
I/O no answer Unit No. -
slot No.
Re
ister
No.
S005
S022
No response from the T2 I/O module has
been received. (Error down)
Check the I/O allocation, the expansion cable
connection and the T2 I/O module mountin
status.
I/O parit
error Unit No. -
slot No.
Re
ister
No.
S005
S023
I/O bus parit
error has been detected in data
read/write for T2 I/O modules. (Error down)
Check the expansion cable connection and
the T2 I/O module mountin
status.
Ille
al I/O re
Unit No. -
slot No.
Re
ister
No.
S005
S021
The allocated I/O re
ister address exceeds
the limit, 32 words. (Error down)
Check the I/O allocation.