LIMITATIONS AND EXCLUSIONS
This limited warranty shall not cover the UPS, UPS part, or BATTERY during their
respective warranty periods, if the following storage, maintenance, installation,
operating conditions are not met throughout the warranty periods (5 conditions
below):
VALVE REGUALATED LEAD ACID (VRLA) BATTERIES FOR TOSHIBA
INTERNATIONAL CORPORATION UPSREQUIRED OPERATING
CONDITIONS
1. Temperature
Annual Average
Temperature 25°C
(77°F)
Temperature per cell < 32°C
(89°F) for more than 30
days
Discharge time Maximum Number of
Cycles (24 months)
30 minutes 69
15 minutes 86
10 minutes 110
2. Maximum number
of full charge/discharge
cycles
5 minutes 130
VALVE REGUALATED LEAD ACID (VRLA) BATTERIES FOT TOSHIBA
INTERNATIONAL CORPORATION UPS
INSTALLATION AND MAINTENANCE CONDITIONS
3. Storage
While UPS is in transit or storage it must always be in
suitable temperature (see condition 1).
4. External Batteries
Parallel battery string applications must be approved
by TIC in writing.
5. Idle Batteries
User must recharge the batteries if not in use
(charged) for more than 6 months.