EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER
74-2958—150
NOTE: The node can be reset b
switchin
the node to
MANUAL and then to the normal operatin
mode
see Fan Operation in Appendix B
.
Also, the Excel 10 variables,
AlarmLogX
where
X
is 1 throu
h
5, that store the last five alarms to occur in the controller, are
available. These points can be viewed throu
h XBS or
E-Vision.
Certain alarm conditions are suppressed conditionall
as
follows:
Broadcasting the Service Message
The Service Messa
e allows a device on the L
ON
W
ORKS
Bus
to be positivel
identified. The Service Messa
e contains the
controller ID number and, therefore, can be used to confirm
the ph
sical location of a particular Excel 10 in a buildin
.
There are three methods of broadcastin
the Service
Messa
e from an Excel 10 W7750 Controller. One uses a
hardware service pin button on the side of the controller
see
Fi
. 41
. The second uses the wall module pushbutton
see
Fi
. 43 and 44
. B
pressin
the wall module pushbutton for
more than four seconds, the controller sends out the Service
Messa
e. The third involves usin
the PC Confi
uration tool,
as follows.
When an
Assign ID
command is issued from the
commissionin
tool, the node
oes into the
SERVICE_MESSAGE mode for five minutes. In the
SERVICE_MESSAGE mode, pressin
the Occupanc
Override button on the remote wall module
refer to Fi
. 43
and 44 for override button location
causes the Service
Messa
e to be broadcast on the network. All other functions
are normal in the SERVICE_MESSAGE mode. Even if an
Excel 10 W7750 Controller does not have an Override button
connected, it can broadcast the Service Messa
e on the
network b
temporaril
shortin
the Controller B
pass Input
terminal to the Sensor Ground terminal on the W7750A,B,C
short terminals 3 and 5
.
The commissionin
tool is used to perform the ID Assi
nment
task
see the E-Vision User’s Guide, form 74-2588
.
Fig. 41. Location of the Service Pin Button.
W7750 Controller Status LED
The LED on the front and center of a W7750 Controller
provides a visual indication of the status of the device. See
Fi
. 42. When the W7750 receives power, the LED should
appear in one of the followin
allowable states:
1.
Off—no power to the processor.
2.
Continuousl
On—processor is in initialized state.
3.
Slow Blink—controllin
, normal state.
4.
Fast Blink—when the Excel 10 has an alarm condition.
LOSS_OF_AIR_FLOW 6 The Fan Status DI indicates that there is no air flow when the node is
commandin
the fan to run. The control is shut down and disabled until power is
c
cled or the node is reset. See NOTE below. The alarm is not issued until
FanFailTime seconds have elapsed since the loss-of-flow condition was first
reported
DIRTY_FILTER 7 The pressure drop across the filter exceeds the limit and the filter re
uires
maintenance. The control runs normall
.
SMOKE_ALARM 8 The smoke detector has detected smoke and the node has entered an
emer
enc
state.
IAQ_OVERRIDE 9 The indoor air
ualit
sensor has detected that the indoor air
ualit
is less than
the desired standard and additional outdoor air is bein
brou
ht into the
conditioned space.
LOW_LIM_ECON_CLOSE 10 The economizer has to close be
ond the minimum position to prevent the
dischar
e air temperature from
oin
below the dischar
e temperature low limit.
Table 12. Excel 10 Alarms. (Continued)
Name of alarm or error bit
Alarm type
number Meaning of alarm code or error bit