A SERVICE OF

logo

Specifications - Analog Input Module
162 HC900 Hybrid Controller Installation and User Guide Revision 5
9/03
Feature Description
A/D resolution
15 bits
Reference Junction Sensing
Via 2 RTDs at top/bottom of module
Update rate
500 ms (Analog to digital converter per module)
Long Term stability
0.1% per year
Channel Configuration Data
Stored in non-volatile memory.
Calibration Data
Data is stored in non-volatile memory
Redundant Factory Calibration
Individual Channel Field Calibration
Diagnostics
Monitoring of Factory Calibration, Field Calibration, 24 Vdc supply, and
configuration.
Channel Configuration Data
Stored in non-volatile memory.