7
Check all factory wiring per the unit wiring
diagram and inspect the factory wiring connec-
tions to be sure none loosened during shipping
or installation.
CAUTION:
To avoid personal injury or property
damage, make certain that the motor
leads cannot come into contact with
any uninsulated metal components
of the unit.
Check all factory wiring per the unit wiring
diagram and inspect the factory wiring connec-
tions to be sure none loosened during shipping
or installation.
CONDENSATE DRAIN
A 3/4” condensate fi tting extends out of the side
of the unit. The drain trap, shipped in the electrical
compartment, must be installed to prevent water
from collecting inside the unit. Thread the elbow
provided with the unit into the drain connection
until hand tight. Install the trap into the fi tting and
seal the joint. Make sure it is level. Route the
condensate from the trap to a suitable drain. Any
connecting tubing or hose must have the outlet
below the trap level for proper drainage.
WARNING:
Turn off electrical power before servic-
ing controls. Severe electrical shock
may result unless power is turned off.
Unit must be installed in compliance
with the National Electrical Code (NEC)
and local codes.
Figure 9. Power Entry
High Voltage
Low Voltage
Figure 8. Drain Trap
Elbow
P-Trap
Figure 7. Standard Motor Lead Connection
If Fixed Torque Motor:
1. Disconnect all electrical power to the unit
and remove the blower panel.
2. Locate the orange and red wires terminated
to the blower motor. The orange wire controls
cooling operation while the red wire controls
heating operation.
3. Verify the required speed from the airfl ow
data found in fi gure 7. Place appropriate wire
on the appropriate motor speed tap for the
required airfl ow point.
Note: If the same speed is required for both
heating and cooling, remove either the red
or orange wire from the blower motor. Next,
obtain the jumper wire from the homeowners
packet and connect it to the blower relays
at the coils on the blue wire and red wire
side.
Model
Wire Color /
Speed Tap
Motor
Speed
Air Flow
(0.3 In. WC)P3RD
2 Ton
Red Low 760
Black High 1000
2.5 Ton
Red Low 760
Black High 1000
3 Ton
Red Low 760
Black High 1000
3.5 Ton
T1 Low 750
T2 Med/Low 1,000
Orange / T3 Medium 1,140
Red / T4 Med/High 1,300
T5 High 1,350
4 Ton
T1 Low 1,340
Orange / T2 Med/Low 1,450
Red / T3 Medium 1,650
T4 Med/High 1,750
T5 High 1,965
5 Ton
T1 Low 1,340
T2 Med/Low 1,450
Orange / T3 Medium 1,650
Red / T4 Med/High 1,750
T5 High 1,965