HP 1200W Power Supply
Part Number - AC
500172-B21
Operational Input Voltage
Range (Vrms)
100 to 240
Frequency Range (Nominal)
(Hz)
50/60
Nominal Input Voltage (Vrms)
100 120 208 200 220 230 240
Maximum Rated Output Wattage
800 900 1200 1200 1200 1200 1200
Nominal Input Current (A rms)
9.7 9.0 7.0 6.8 6.4 9.1 5.9
Max Rated Input Wattage Rating
(Watts)
930 1034 1348 1348 1348 1348 1348
Max. Rated VA (Volt-Amp)
970 1079 1406 1406 1406 1406 1406
Efficiency (%) at Max. Rated
Output Wattage
86 87 89 89 89 89 89
Power Factor
0.97 0.97 0.97 0.97 0.97 0.97 0.97
Leakage Current (mA)
0.42 0.50 0.83 0.87 0.92 0.96 1.00
Max. Inrush Current (A peak)
30 30 30 30 30 30 30
Max. Inrush Current duration
(mS)
20 20 20 20 20 20 20
Maximum British Thermal Unit
Rating (BTU-Hr)
3174 3530 4600 4600 4600 4600 4600
HP 1200W PSU 48VDC Input Part Number
437573-B21
Input Voltage Range (DCV)
36-72
Frequency Range (Nominal) (Hz)
DC
Nominal Input Voltage (VDC)
36 48 72
Maximum Rated Output Wattage
1200 1200 1200
Nominal Input Current (ACD)
38 28 19
Max Rated Input Wattage Rating (Watts)
1380 1350 1365
Max. Rated VA (Volt-Amp)
1380 1350 1365
Efficiency (%) at Max. Rated Output Wattage
87 89 88
Power Factor
N/A N/A N/A
Leakage Current (mA)
N/A N/A N/A
Max. Inrush Current (A peak)
20 25 35
Max. Inrush Current duration (mS)
1 1 3
Maximum British Thermal Unit Rating (BTU-Hr)
4713 4610 4662
NOTES:
To review typical system power ratings use the HP Power Advisor which is available online located at url:
www.hp.com/go/proliant-energy-efficient
or
www.hp.com/go/hppoweradvisor
QuickSpecs
HP ProLiant DL380 Generation 6
Power Specifications
DA - 13234 Worldwide QuickSpecs — Version 16 — 8.28.2009
Page 46