9
9
00 Address
If you are using Communications Mode 0 or 1, and you are installing more than one thermostat, each must be
set to a consecutive address, starting at 1. The default address setting is 1.
An address from 1- 127 may be selected.
01 Communications mode
The thermostat can communicate with remote systems in 4 different modes. These modes are:
0 300 baud, RS-232 mode (for use with personal computers)
1 100 baud, Z-Wave mode (OmniLT, Omni, Omni II, OmniPro, and OmniPro II systems)
8 PESM mode, (use with Model 1503 automation systems)
24 Day/Night mode (for use with remote setback switch)
The default setting is 1.
02 System options
The thermostat can be configured with the following system options:
0 Auto changeover no fan with heat
1 Auto changeover fan on with heat
4 Manual changeover no fan with heat
5 Manual changeover fan on with heat
12 Heat only no fan with heat
13 Heat only fan on with heat
20 Cool only
The default setting is 0.
03 Display options
The thermostat can be configured to display the following attributes:
0 Celsius am/pm time format programmable
1 Fahrenheit am/pm time format programmable
2 Celsius 24-hour time format programmable
3 Fahrenheit 24-hour time format programmable
4 Celsius am/pm time format non-programmable
5 Fahrenheit am/pm time format non-programmable
6 Celsius 24-hour time format non-programmable
7 Fahrenheit 24-hour time format non-programmable
When communicating with an HAI controller, the thermostat should be configured as "non-programmable". To
disable the clock and filter reminder displays, add “16” to each value.
The default setting is 1.