45
Operation
|
Table 7. Settings (continued)
Description Default SettingAvailable Settings
Synchronization Window [Sync Disabled] [±0.5 Hz] [±1.0 Hz] [±1.5 Hz]
[±2.0 Hz] [±2.5 Hz] [±3.0 Hz]
If ±3.0 Hz, on inverter operation the inverter tries to
synchronize with the Bypass when the Bypass
frequency is not more than 3 Hz from the nominal
output frequency; otherwise, the inverter goes to
nominal frequency. On Bypass mode, the sync
window is always ±3 Hz.
NOTE: In Sync Disabled state, if the Bypass
operation is allowed, the UPS synchronizes only
when it is operating on Bypass mode.
±3.0 Hz
Unsynchronized Transfers [Enabled] [Disabled]
If Enabled, unsynchronized transfers to the Bypass
are allowed.
If Disabled, unsynchronized transfers to the Bypass
are not allowed.
NOTE: The Qualify Bypass setting may overrule the
Unsynchronized Transfers setting.
Enabled
External Battery Modules (EBMs) [0] [1]
See “Configuring the UPS for an EBM” on page 52.
0
Charger [Enabled] [Disabled]
If Enabled, batteries charge normally.
If Disabled, the battery charger is off.
Enabled
Battery Charge % to Restart [0%] [10%] [20%] [30%]...[100%]
When enabled, automatic restart is made when the
battery charge state reaches the selected level. If set
to 0%, the feature is disabled.
0%
Battery Low Alarm [Immediate] [2 min] [3 min] [5 min]
If you select a value, the battery low alarm triggers
when the set amount of backup time
(approximately) remains in the batteries.
3 min
Automatic Battery Tests [Enabled] [Disabled]
See “Running Automatic Battery Tests” on page 53.
Enabled