York K2EU060 Air Conditioner User Manual


 
036-21300-002-A-0905
Unitary Products Group 23
TABLE 22: KEU ELECTRICAL DATA (CONTINUED)
Model
(TONS)
Power
Supply
Voltage
Indoor
Motor
FLA
Heater
Model
Number
Nominal
Heater
KW
Applied
Heater KW
Electric
Heat Amps
Min.
Circuit
Ampacity
(AMPS)
Max. Fuse
1
/
HACR
Breaker
2
(AMPS)
180
(15)
208 10.6
None -- -- -- 13.3 20
2HS04501025 10 7.5 20.8 39.3 40
2HS04501625 16 12.0 33.4 54.9 60
2HS04502625 26 19.5 54.2 81.0 90
2HS04503625 36 27.0 75.1 107.1 110
2HS04507225 72 54.1 150.1 200.9 225
240 9.6
None -- -- -- 12.0 15
2HS04501025 10 10.0 24.1 42.1 45
2HS04501625 16 16.0 38.5 60.1 70
2HS04502625 26 26.0 62.5 90.2 100
2HS04503625 36 36.0 86.6 120.3 125
2HS04507225 72 72.0 173.2 228.5 250
460 4.8
None -- -- -- 6.0 15
2HS04501046 10 10.0 12.0 21.0 25
2HS04501646 16 16.0 19.2 30.1 35
2HS04502646 26 26.0 31.3 45.1 50
2HS04503646 36 36.0 43.3 60.1 70
2HS04507246 72 72.0 86.6 114.3 125
575 3.9
None -- -- -- 4.9 15
2HS04501058 10 10.0 9.6 16.9 20
2HS04501658 16 16.0 15.4 24.1 25
2HS04502658 26 26.0 25.0 36.1 40
2HS04503658 36 36.0 34.6 48.2 50
2HS04507258 72 72.0 69.3 91.5 100
1. Dual element time delay.
2. HACR type per NEC.
3. The K*EU060 indoor motor is single phase. The electrical heaters MUST be supplied with 3-phase voltage only.