York DY 060 Air Conditioner User Manual


 
343615-YTG-B-0308
Johnson Controls Unitary Products 21
060
(5.0)
208-1-60 28.8 145.0 45.0 2.3 7.6 0.0
None - - - 45.9 50
E05 4.0 1 19.2 45.9 50
E07 5.6 1 26.9 45.9 50
E10 8.0 1 38.5 57.6 60
E15 11.9 2 57.2 81.0 90
E20 15.9 2 76.4 105.1 110
E30 22.2 2 106.7 142.9 150
230-1-60 28.8 145.0 45.0 2.3 7.6 0.0
None - - - 45.9 50
E05 5.3 1 23.0 45.9 50
E07 7.5 1 32.6 48.6 50
E10 10.6 1 46.1 64.7 70
E15 15.9 2 69.1 92.3 100
E20 21.2 2 92.2 119.9 125
E30 29.6 2 128.7 163.7 175
208-3-60 17.3 123.0 27.0 2.3 7.6 0.0
None - - - 31.5 35
E05 4.0 1 11.1 31.5 35
E07 5.6 1 15.5 31.5 35
E10 8.0 1 22.2 37.3 40
E15 11.9 2 33.0 50.8 60
E20 15.9 2 44.1 64.7 70
E30 22.2 2 61.6 86.5 90
230-3-60 17.3 123.0 27.0 2.3 7.6 0.0
None - - - 31.5 35
E05 5.3 1 13.3 31.5 35
E07 7.5 1 18.8 32.1 35
E10 10.6 1 26.6 41.4 45
E15 15.9 2 39.9 57.3 60
E20 21.2 2 53.2 73.2 80
E30 29.6 2 74.3 98.5 100
460-3-60 9.6 70.0 15.0 1.3 7.6 0.0
None - - - 17.1 20
E07 6.8 1 8.5 17.1 20
E10 10.1 1 12.7 19.9 20
E15 13.6 2 17.1 25.2 25
E20 19.5 2 24.5 34.1 35
E30 28.8 2 36.1 48.1 50
575-3-60 7.4 53.0 11.5 1.3 7.6 0.0
None - - - 13.3 15
E10 10.6 1 10.6 16.5 20
E15 15.9 1 16.0 22.9 25
E20 21.2 2 21.3 29.3 30
E30 30.4 2 30.5 40.4 40
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
TABLE 23: ELECTRICAL DATA - DY036, 048 & 060 DIRECT DRIVE W/O POWERED CONVENIENCE OUTLET (CONT)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max
Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC FLA FLA FLA Model kW Stages Amps