York DNH018 Air Conditioner User Manual


 
036-21233-002-A-0903
Unitary Products Group 15
TABLE 10: SIDE SUPPLY AIR PERFORMANCE - 208 VOLT
1
MODEL #
DNH
(Cooling/
Heating)
MTR
SPD
EXTERNAL STAIC PRESSURE - IWG
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 1.10
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
018
HI------------ ----608358465326--
MED - - - - - - - - - - 695 263 615 246 509 226 - - - - - -
LOW 743 243 700 235 657 226 614 218 549 207 483 195 - - - - - - - - - -
024
HI - - - - - - - - - - 984 443 894 422 751 390 608 358 - - - -
MED 994 333 947 321 901 309 854 297 774 280 695 263 615 246 - - - - - - - -
LOW 743 243 700 235 657 226 614 218 - - - - - - - - - - - - - -
030
HI - - - - 1238 504 1165 484 1075 463 984 443 894 422 751 390 - - - - - -
MED 994 333 947 321 901 309 854 297 774 280 - - - - - - - - - - - -
LOW----------------------
036
HI - - - - - - - - 1465 712 1390 685 1315 657 1204 623 1093 588 982 554 - -
MED 1432 650 1381 628 1330 605 1279 583 1210 556 1140 529 1071 502 977 477 - - - - - -
LOW 1191 527 1149 510 1107 494 1065 477 1009 459 952 441 - - - - - - - - - -
042
HI - - 1681 797 1610 768 1540 740 1465 712 1390 685 1315 657 1204 623 1093 588 - - - -
MED 1432 650 1381 628 1330 605 1279 583 1210 556 1140 529 - - - - - - - - - -
LOW1191527114951011074941065477--------------
048
HI 1742 898 1695 869 1648 841 1601 811 1555 781 1501 747 1446 714 1317 667 - - - - - -
MED 1523 750 1498 730 1473 710 1447 692 1421 673 1371 647 1320 620 1211 580 - - - - - -
LOW 1343 620 1327 606 1310 593 1280 573 1250 553 - - - - - - - - - - - -
060
(3 tube)
HEAT 1500 245 1500 297 1500 348 1500 400 1500 470 1500 540 1500 610 1500 680 1500 750 1500 820 1500 890
060
(4 & 5
tube)
HEAT 1700 390 1700 443 1700 497 1700 550 1700 620 1700 690 1700 760 1700 830 1700 900 - - - -
060
(factory
setting)
COOL 1800 460 1800 515 1800 570 1800 625 1800 690 1800 755 1800 820 1800 962 - - - - - -
060
(field
setting)
COOL 2000 640 2000 700 2000 760 2000 820 2000 928 - - - - - - - - - - - -
1.
Above data includes allowances for a dry evaporator coil, gas heat exchanger and no filters. For additional pressure drops, refer to
Table 14 and 15.