York DM 072 Air Conditioner User Manual


 
036-21502-003-A-1105
26 Unitary Products Group
TABLE 17: ELECTRICAL DATA - DM036 & 048 DIRECT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET
NONE 0.0 0.0 28.2 45
2CE04510506 4.0 19.2 29.5 45
2CE04510706 5.6 26.9 39.2 45
2CE04511006 8.0 38.5 53.6 60
2CE04511506 11.9 57.2 77.0 80
2CE04512006 15.9 76.4 101.1 110
NONE 0.0 0.0 28.2 45
2CE04510506 5.3 22.1 33.1 45
2CE04510706 7.5 31.3 44.6 45
2CE04511006 10.6 44.2 60.7 70
2CE04511506 15.9 66.3 88.3 90
2CE04512006 21.2 88.3 115.9 125
NONE 0.0 0.0 19.9 30
2CE04510525
2
4.0 11.1 19.9 30
2CE04510725
2
5.6 15.5 24.9 30
2CE04511025 8.0 22.2 33.3 35
2CE04511525 11.9 33.0 46.8 50
2CE04512025 15.9 44.1 60.7 70
NONE 0.0 0.0 19.9 30
2CE04510525
2
5.3 12.7 21.4 30
2CE04510725
2
7.5 18.0 28.1 30
2CE04511025 10.6 25.5 37.4 40
2CE04511525 15.9 38.2 53.3 60
2CE04512025 21.2 51.0 69.2 70
NONE 0.0 0.0 10.8 15
2CE04510746
2
6.8 8.2 13.0 15
2CE04511046
2
10.1 12.1 17.9 20
2CE04511546
2
13.6 16.4 23.2 25
2CE04512046
2
19.5 23.5 32.1 35
NONE 0.0 0.0 8.7 15
2CE04511058 10.6 10.2 14.9 15
2CE04511558 15.9 15.3 21.3 25
2CE04512058 21.2 20.4 27.7 30
NONE 0.0 0.0 36.8 60
2CE04510506 4.0 19.2 36.8 60
2CE04510706 5.6 26.9 39.9 60
2CE04511006 8.0 38.5 54.3 60
2CE04511506 11.9 57.2 77.8 80
2CE04512006 15.9 76.4 101.8 110
NONE 0.0 0.0 36.8 60
2CE04510506 5.3 22.1 36.8 60
2CE04510706 7.5 31.3 45.3 60
2CE04511006 10.6 44.2 61.5 70
2CE04511506 15.9 66.3 89.1 90
2CE04512006 21.2 88.3 116.7 125
NONE 0.0 0.0 23.9 35
2CE04510525
2
4.0 11.1 23.9 35
2CE04510725
2
5.6 15.5 25.7 35
2CE04511025 8.0 22.2 34.0 35
2CE04511525 11.9 33.0 47.5 50
2CE04512025 15.9 44.1 61.4 70
NONE 0.0 0.0 23.9 35
2CE04510525
2
5.3 12.7 23.9 35
2CE04510725
2
7.5 18.0 28.8 35
2CE04511025 10.6 25.5 38.1 40
2CE04511525 15.9 38.2 54.1 60
2CE04512025 21.2 51.0 70.0 70
NONE 0.0 0.0 11.9 15
2CE04510746
2
6.8 8.2 13.0 15
2CE04511046
2
10.1 12.1 17.9 20
2CE04511546
2
13.6 16.4 23.2 25
2CE04512046
2
19.5 23.5 32.1 35
NONE 0.0 0.0 9.7 15
2CE04511058 10.6 10.2 14.9 15
2CE04511558 15.9 15.3 21.3 25
2CE04512058 21.2 20.4 27.7 30
Model
Tonnage
Voltage
Compressors
3
45
Max Fuse /
BRKR
1
Size
Amps
RLA
Each
LRA
Each
ID Blower
Motor
FLA
Conv
Outlet
Amps
Electric Heater
Model No.
Heater
kW
OD Fan
Motor
FLA
Heater
Amps
Minimum
Circuit
Ampacity
Amps
1.3
1.3
0.8
105
90
4.4 0.0
230-1-60 18.0 105 1.3 4.4 0.0
208-1-60 18.0
4.4 0.0
230-3-60 11.4 90 1.3 4.4 0.0
208-3-60 11.4
2.2 0.0
575-3-60 5.0 36 0.8 2.2 0.0
460-3-60 6.2
4
208-1-60 24.4 140
208-3-60 14.1 105
460-3-60 7.1 55
1.3 5.0 0.0
230-1-60 24.4 140 1.3 5.0 0.0
1.3 5.0 0.0
230-3-60 14.1 105 1.3 5.0 0.0
575-3-60 5.8 44 0.8
0.0
2.2 0.0
0.8 2.2
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.