York DM 060 Air Conditioner User Manual


 
036-21502-003-A-1105
40 Unitary Products Group
FIGURE 10 - FOUR AND SIX POINT LOADING
44
7
/
8
82
1
/
4
Y
X
A
B
C
D
CONDENSER COIL
END OF UNIT
FRONT OF UNIT
APPROXIMATE
CENTER OF GRAVITY
BACK OF UNIT
44
7
/
8
82
1
/
4
Y
X
A
B
C
D
E
F
CONDENSER COIL
END OF UNIT
FRONT OF UNIT
APPROXIMATE
CENTER OF GRAVITY
BACK OF UNIT
TABLE 30: DM 4 AND 6 POINT LOADS WEIGHT DISTRIBUTION
UNIT TOTAL
4-Point Loading (lb) 6-Point Loading (lb)
ABCDABCDEF
DM036 Cooling/ Electric 565
125123157 160848382 104 105 107
DM036N04 605
134 132 168171908988112 113 114
DM036D06 615
137 134 171174919089113115116
DM036N08 625
139 136 173177 93 92 91 115 117 118
DM036D10 635
141 138 176 179949392 117 119 120
DM048 Cooling/ Electric 615
137 134 171174919089113115116
DM048(D,N)06 665
148 145 184 188 99 98 96 123124126
DM048(D,N)10 685
152 149 190 194 102 100 99 126 128129
DM060 Cooling/ Electric 640
142 140 178 181 95 94 93 118 119 121
DM060D06 690
153 150 191 195 102 101 100 127 129130
DM060N08 700
155 153 194 198 104 103 101 129131132
DM060(D,N)10 710
158 155 197201 105 104 103 131 132 134
DM072 Cooling/ Electric 720
160157200 203 107 106 104 133 134 136
DM072D06 770
171168 214 218 114 113 112 142 144 145
DM072N08 780
173170 216220116 114 113 144 146 147
DM072(D,N)10 790
175172 219 223117 116 114 146 147 149
TABLE 31: CENTER OF GRAVITY
DIMENSION 3 - 5 TON 6 TON
X 40-¾ 44
Y 19-¾ 22”