York DM072 Air Conditioner User Manual


 
392856-YTG-B-0708
Johnson Controls Unitary Products 13
TABLE 14: ELECTRICAL DATA - DM072 DIRECT DRIVE W/O POWERED CONV. OUTLET
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
1. Minimum Circuit Ampacity.
Max
Fuse
2
/
Breaker
3
Size
(Amps)
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
RLA LRA MCC FLA FLA FLA Model kW Stages Amps
072
(6.0)
208-3-60 18.9 146.0 29.5 1.3 6.8 0.0
None - - - 31.7 40
E05 4.0 1 11.1 31.7 40
E07 5.6 1 15.5 31.7 40
E10 8.0 1 22.2 36.3 50
E15 11.9 2 33.0 49.8 50
E20 15.9 2 44.1 63.7 70
E30 22.2 2 61.6 85.5 90
230-3-60 18.9 146.0 29.5 1.3 6.8 0.0
None - - - 31.7 40
E05 5.3 1 13.3 31.7 40
E07 7.5 1 18.8 31.7 40
E10 10.6 1 26.6 40.4 50
E15 15.9 2 39.9 56.3 60
E20 21.2 2 53.2 72.2 80
E30 29.6 2 74.3 97.5 100
460-3-60 9.5 73.0 14.8 0.8 3.6 0.0
None - - - 16.3 25
E07 6.8 1 8.5 16.3 25
E10 10.1 1 12.7 19.7 25
E15 13.6 2 17.1 24.9 25
E20 19.5 2 24.5 33.8 35
E30 28.8 2 36.1 47.8 50
575-3-60 7.6 58.4 11.8 0.8 3.6 0.0
None - - - 13.0 15
E10 10.6 1 10.6 16.3 20
E15 15.9 1 16.0 22.7 25
E20 21.2 2 21.3 29.1 30
E30 30.4 2 30.5 40.2 40
TABLE 15: ELECTRICAL DATA - DM072 BELT DRIVE W/O POWERED CONV. OUTLET
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
1. Minimum Circuit Ampacity.
Max
Fuse
2
/
Breaker
3
Size
(Amps)
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
RLA LRA MCC FLA FLA FLA Model kW Stages Amps
072
(6.0)
208-3-60 18.9 146.0 29.5 1.3 5.0 0.0
None - - - 29.9 40
E05 4.0 1 11.1 29.9 40
E07 5.6 1 15.5 29.9 40
E10 8.0 1 22.2 34.0 45
E15 11.9 2 33.0 47.5 50
E20 15.9 2 44.1 61.4 70
E30 22.2 2 61.6 83.3 90
230-3-60 18.9 146.0 29.5 1.3 5.0 0.0
None - - - 29.9 40
E05 5.3 1 13.3 29.9 40
E07 7.5 1 18.8 29.9 40
E10 10.6 1 26.6 38.1 45
E15 15.9 2 39.9 54.1 60
E20 21.2 2 53.2 70.0 70
E30 29.6 2 74.3 95.3 100
460-3-60 9.5 73.0 14.8 0.8 2.5 0.0
None - - - 15.2 20
E07 6.8 1 8.5 15.2 20
E10 10.1 1 12.7 18.3 20
E15 13.6 2 17.1 23.6 25
E20 19.5 2 24.5 32.4 35
E30 28.8 2 36.1 46.4 50
575-3-60 7.6 58.4 11.8 0.8 2.0 0.0
None - - - 12.1 15
E10 10.6 1 10.6 15.2 20
E15 15.9 1 16.0 21.6 25
E20 21.2 2 21.3 28.0 30
E30 30.4 2 30.5 39.1 40