York DH 036 Air Conditioner User Manual


 
254597-YTG-B-0507
Unitary Products Group 15
TABLE 15: ELECTRICAL DATA - DH036, 048 & 060 DIRECT DRIVE W/O POWERED CONVENIENCE OUTLET
MODEL
TONNAGE
VOLTAGE
COMPRESSORS
OD FAN
MOTOR
FLA
ID
BLOWER
MOTOR
FLA
CONV
OUTLET
FLA
ELECTRIC HEATER
MODEL NO.
HEATER
KW
HEATER
AMPS
MIN.
CIRCUIT
AMPACITY
(AMPS)
MAX. FUSE/
BRKR
1
SIZE
(AMPS)
RLA
EACH
LRA
EACH
DH036
208-3-60 13.1 110.0 2.3 8.0 0.0
None -- -- 26.7 35
2CE04510525
2
4.0 11.1 26.7 35
2CE04510725
2
5.6 15.5 29.4 35
2CE04511025 8.0 22.2 37.8 40
2CE04511525 11.9 33.0 51.3 60
2CE04512025 15.9 44.1 65.2 70
230-3-60 13.1 110.0 2.3 8.0 0.0
None -- -- 26.7 35
2CE04510525
2
5.3 12.7 26.7 35
2CE04510725
2
7.5 18.0 32.6 35
2CE04511025 10.6 25.5 41.9 45
2CE04511525 15.9 38.2 57.8 60
2CE04512025 21.2 51.0 73.7 80
DH048
208-3-60 13.1 110.0 2.3 10.6 0.0
None -- -- 29.3 40
2CE04510525
2
4.0 11.1 29.3 40
2CE04510725
2
5.6 15.5 32.7 40
2CE04511025 8.0 22.2 41.0 45
2CE04511525 11.9 33.0 54.5 60
2CE04512025 15.9 44.1 68.4 70
230-3-60 13.1 110.0 2.3 10.6 0.0
None -- -- 29.3 40
2CE04510525
2
5.3 12.7 29.3 40
2CE04510725
2
7.5 18.0 35.8 40
2CE04511025 10.6 25.5 45.1 50
2CE04511525 15.9 38.2 61.1 70
2CE04512025 21.2 51.0 77.0 80
DH060
208-3-60 16.0 137.0 2.3 10.6 0.0
None -- -- 32.9 45
2CE04510525
2
4.0 11.1 32.9 45
2CE04510725
2
5.6 15.5 32.9 45
2CE04511025 8.0 22.2 41.0 45
2CE04511525 11.9 33.0 54.5 60
2CE04512025 15.9 44.1 68.4 70
2CE04513025 22.2 61.6 90.3 100
230-3-60 16.0 137.0 2.3 10.6 0.0
None -- -- 32.9 45
2CE04510525
2
5.3 12.7 32.9 45
2CE04510725
2
7.5 18.0 35.8 45
2CE04511025 10.6 25.5 45.1 50
2CE04511525 15.9 38.2 61.1 70
2CE04512025 21.2 51.0 77.0 80
2CE04513025 29.6 71.2 102.3 110
1. HACR Type per NEC.
2. These electric heaters do not include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block
accessories 2FB04700825 and 2FB04700846 are available for field installation.