York D2EB Air Conditioner User Manual


 
174065-YIM-A-0206
6 Unitary Products Group
DEB
POWER
SUPPLY
COMPRESSOR
COND.
FAN
MOTOR
FLA
SUPPLY
AIR
BLOWER
MOTOR,
FLA
ELECTRIC HEAT ACCESSORY
MINIMUM
CIRCUIT
AMPACITY
MAX.
FUSE
SIZE,
1
AMPS
MAX.
HACR
2
BREAKER
SIZE
MODEL
RLA LRA MODEL NO.
STAGE
KW
TOTAL
AMPS
018 208/230-1-60 9.0 48.0 1.1 2.6
2NH04500506
2NH04500706
1
2
3.8/5.0 *
5.6/7.5 *
18.1/20.8
27.1/31.3
25.8/29.3
37.1/42.3
30/30
40/45
30/30
40/45
024 208/230-1-60 11.2 60.0 1.1 2.6
2NH04500506
2NH04500706
2NH04501006
1
2
2
3.8/5.0 *
5.6/7.5 *
7.5/10.0 *
18.1/20.8
27.1/31.3
36.1/41.7
25.8/29.3
37.1/42.3
48.4/55.3
30/30
40/45
50/60
30/30
40/45
50/60
030 208/230-1-60 12.0 73.0 1.1 2.6
2NH04500506
2NH04500706
2NH04501006
2NH04501506
1
2
2
2
3.8/5.0 *
5.6/7.5 *
7.5/10.0 *
11.3/15.0 *
18.1/20.8
27.3/31.3
36.1/41.7
54.2/62.5
25.8/29.3
37.1/42.3
48.4/55.3
71.0/81.4
30/30
40/45
50/60
80/90
30/30
40/45
50/60
80/90
036 208/230-1-60 17.3 94.0 1.1 3.5
2NH04501006
2NH04501506
2
2
7.5/10.0 *
11.3/15.0 *
36.1/41.7
54.2/62.5
49.5/56.5
72.1/82.5
50/60
80/90
50/60
80/90
042 208/230-1-60 20.5 120.0 1.1 3.5
2NH04500506
2NH04500706
2NH04501006
2NH04501506
1
2
2
2
3.8/5.0 *
5.6/7.5 *
7.5/10.0 *
11.3/15.0 *
18.1/20.8
27.1/31.3
36.1/41.7
54.2/62.5
30.2/30.4
38.2/43.4
49.5/56.5
72.1/82.5
40/40
50/50
50/60
80/90
40/40
50/50
50/60
80/90
048 208/230-1-60 24.4 140.0 1.3 4.0
2NH04501006
2NH04501506
2NH04502006
2NH04502506
2
2
2
2
7.5/10.0 *
11.3/15.0 *
15.0/20.0 *
18.8/25.0 *
36.1/41.7
54.2/62.5
72.2/83.3
90.3/104.2
50.1/57.1
72.1/83.1
95.3/109.2
117.8/135.2
60/60
80/90
100/110
125/150
60/60
80/90
100/110
125/150
060 208/230-1-60 28.9 165.0 1.3 7.0
2NH04501006
2NH04501506
2NH04502006
2NH04502506
2
2
2
2
7.5/10.0 *
11.3/15.0 *
15.0/20.0 *
18.8/25.0 *
36.1/41.7
54.2/62.5
72.2/83.3
90.3/104.2
53.9/60.8
76.5/86.9
99.0/112.9
121.6/139.0
70/70
80/90
100/125
125/150
70/70
80/90
100/125
125/150
= Dual element, time delay type. * = KW listed is for 240 volts, use table on previous page for 208 or 230 volts.
= Standard circuit breakers may be used in Canada and on applications ** = KW listed is for 480 volts, use table on previous page for 460 volts.
over 60 amps where the heaters are separately fused.
TABLE 5 - ELECTRICAL DATA (COOLING / ELECTRIC HEAT)