York B1HP024 THRU 048 Heat Pump User Manual


 
036-21528-001-A-0303
16 Unitary Products Group
TABLE 15: ELECTRICAL DATA (BASIC UNIT)
MODEL
BHP
POWER
SUPPLY
VOLTAGE
LIMITATIONS
1
COMPRESSOR
OUTDOOR
FAN
MOTOR,
FLA
SUPPLY AIR
BLOWER
MOTOR,
FLA
MINIMUM
CIRCUIT
AMPACITY
MAX
FUSE
SIZE,
AMPS
2
MAX.
HACR
BREAKER
SIZE,
AMPS
UNIT
POWER
FACTOR
TRANSFORMER
SIZE (VA)
MIN. MAX. RLA LRA
024 208/230-1-60 187 253 9.3 57.0 1.1 5.0 17.7 25 25 0.96 40
030
208/230-1-60 187 253 15.0 72.5 1.1 5.0 24.9 35 35 0.96 40
208/230-3-60 187 253 10.0 63.0 1.1 5.0 18.6 25 25 0.96 75
460-3-60 414 504 5.0 31.0 0.6 5.0 11.9 15 15 0.96 75
036
208/230-1-60 187 253 17.2 94.0 1.1 7.3 29.9 45 45 0.96 40
208/230-3-60 187 253 11.4 78.0 1.1 7.3 22.7 30 30 0.96 75
460-3-60 414 504 5.7 40.0 0.6 7.3 15.4 20 20 0.96 75
042
208/230-1-60 187 253 20.0 104.0 1.1 7.3 33.4 50 50 0.96 40
208/230-3-60 187 253 13.9 88.0 1.1 7.3 25.8 35 35 0.96 75
460-3-60 414 504 6.4 44.0 0.6 7.3 16.1 20 20 0.96 75
048
208/230-1-60 187 253 23.4 126.0 1.5 7.3 38.1 60 60 0.96 40
208/230-3-60 187 253 13.0 93.0 1.5 7.3 25.1 35 35 0.96 75
460-3-60 414 504 6.4 46.5 0.8 7.3 16.3 20 20 0.96 75
1.
Rated in accordance with ARI Standard 100, utilization range ìAî.
2.
Dual element, time delay type.
ELECTRIC HEAT
CORRECTION
FACTORS
NOMINAL VOLTAGE VOLTAGE KW CAP. MULTIPLIER
240
208
230
0.75
0.92
480 460 0.92