339293-YTG-C-0208
6 Unitary Products Group
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87°F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. H1RA024S78A
INDOOR COIL MODEL NO. F2RP024
CONDENSER
ENTERING AIR
TEMPERATURE
IDCFM 650 850 1050
ID DB (°F) 85 80 70 85 80 70 85 80 70
ID WB (°F) 72 67 57 72 67 57 72 67 57
75
T.C. 26.4 25.3 24.0 26.6 25.7 24.6 26.7 26.1 25.2
S.C. 15.4 15.6 15.4 16.2 16.7 16.8 16.9 17.8 18.2
K.W 2.15 2.11 2.08 2.17 2.13 2.10 2.18 2.15 2.12
85
T.C. 25.4 23.9 21.8 25.7 24.6 22.8 26.1 25.2 23.7
S.C. 15.3 15.1 14.4 16.4 16.6 16.2 17.4 18.2 18.1
K.W 2.312.261.162.332.282.232.362.312.26
95
T.C. 24.4 22.5 19.6 24.9 23.4 20.9 25.4 24.3 22.2
S.C. 15.3 14.6 13.4 16.6 16.6 15.7 17.9 18.5 17.9
K.W 2.472.402.312.502.442.352.532.472.39
105
T.C. 22.5 20.1 17.6 23.2 21.1 18.6 23.9 22.1 19.6
S.C. 14.7 13.8 12.7 16.4 15.9 14.7 18.1 17.9 16.8
K.W 2.622.532.442.662.572.472.702.612.51
115
T.C. 20.6 17.7 15.6 21.5 18.8 16.3 22.4 19.8 16.9
S.C. 14.2 13.0 11.9 16.3 15.2 13.8 18.3 17.3 15.6
K.W 2.762.652.562.812.702.592.862.742.62
125
T.C. 17.8 15.2 13.3 18.7 15.9 14.0 19.5 16.7 14.7
S.C. 13.3 12.4 11.4 15.4 14.3 13.1 17.4 16.1 14.7
K.W 2.892.782.692.942.822.722.992.852.75
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.