White Rodgers T7351F Thermostat User Manual


 
Commercial VisionPRO
®
8000, Commercial PRO
®
7000 And MultiPRO
Applications
Remote Sensing
CanbeconfiguredusingHoneywell’slineof10Kohmand
20Kohmcommercialsensors,supportingthefollowing
applicationsthatresidentialthermostatsdon’t:
• TemperatureAveragingNetworks
Because commercial thermostats can be configured
toa20Kohmnetwork,temperatureaveragenetworks
ofanywherefrom1to9+sensorscanbedeployed.
Combinationsof10Kohmand20Kohmsensorsare
use to create the averaging network. The most popular
sensorsaretheTR21andTR21-A(averaging)10Ksensor
andtheTR21andTR21-A20Ksensor.
• RoomTemperatureControl
Performed via a sensing network using the following
sensors:
– WallSensors:TR21-A(10K)foraveragingonly,
TR21(20K),C7189U1005(10K)
– FlushMountSensors:C7772A1012(20K)
– ButtonSensors:C7041P(20K)
• DuctReturnTemperatureControl
Performedusingthefollowing20Ksensors:
C7041B/C7041C/C7770A/C7041J
Unit Vent
• CanbeprogrammedtocontrolASHRAECycle1unitvent
applications.
• Unitventoutside-airdampercanbeprogrammedthrough
the Economizer feature. When the unit vent is on and
occupied, the thermostat will enable the economizer
relay to keep the outside air damper at the maximum
percentage opening. Only maximum percentage
opening is available; the thermostat will not modulate
the damper. When the unit vent is unoccupied, the
thermostat will close the damper.
• RangeStopfeaturecanbeconfiguredtoprogramalow
limit setpoint to prevent equipment damage from freezing.
Commercial Codes
• Complywithcommercialbuildingcodesandmeetthemost
rigorousstandard,California’sTitle24.
• Noholdbuttonisavailable,sothethermostatremains
in permanent schedule.
• Overridebuttonallowsthetenanttooverridean
unoccupied mode for up to 4 hours and can be configured
foranexactoverridesetpoint.Dependingonthepartial
lockout level deployed, a user may override to an exact
setpoint or be given a setpoint range to choose from.
• Pre-OccupancyPurgeandEconomizerfunctionsallow
the building owner to meet all HVAC ventilation codes for
commercial buildings.
Lighting Load Reduction (TOD)
• Commercialbuildingsarefrequentlyautomatedtoturnoff
lighting loads. Lighting loads can use even more energy
than HVAC systems in commercial buildings, and 79%
of commercial buildings have off-hours lighting load
reductioncontrol.Byusingthetime-of-dayrelay(TOD)
inconjunctionwithalightingcontrolsystem,userscan
automatetheirlightingloads.(NotavailableonMultiPRO
)
SUBBASE
15
TR21
TR21
TR21-A
THE TR21-A IS A 10K OHM SENSOR