5
* NOTE: COMP LOCK OFF permanently
defeats compressor lockout. You must turn
this selection ON if you do not have a
system that already provides compressor
short-cycle protection. Please see “Lockout
Bypass Option” to temporarily override
compressor lockout.
INSTALLER TABLE
1 MLTI STG HEAT PUMP
2 HEAT PUMP
(1)
2 or 3
Selects type of system. Selecting HEAT PUMP
makes additional menu items for heat pump
system available.
3 ELECT HEAT FAN
(ON)
OFF
Fan cycles with call for heat if ON. Fan always
cycles with pump stages.
4 SET CYCLE HEAT
(5 for multi-stage
13 for heat pump)
1 to 40 for multi-stage
9 to 40 for heat pump
5 SET CYCLE COOL
(13)
9 to 40
12
ECON
(OFF)
ON
15 REM SEN b
(OFF)
ON
16 REM SEN C
(OFF)
ON
Returns to normal operation
17 STAT SEN L
(ON)
OFF
13 HEAT-OFF-COOL-AUTO
or
HEAT-EMER-OFF-COOL-
AUTO (for heat pumps)
HEAT-OFF-COOL
or
HEAT-EMER-OFF-COOL
(for heat pumps)
14 REM SEN A
(OFF)
ON
Selects Remote Sensor A (connected to SA) if ON.
Selects:
1. one compressor on Y1.
2. two compressors on Y1, Y2.
3. one compressor on W1.
Selects HEAT anticipation adjustment.
Selects COOL anticipation adjustment.
Allows selection of HEAT and COOL or HEAT,
COOL and AUTO with SYSTEM button.
(EMER appears in sequence after HEAT if HEAT
PUMP is selected.)
Economizer option. Long Y1 cycles for cooling
with outdoor air
Selects Remote Sensor B (connected to SB) if ON.
Selects Remote Sensor C (connected to SC) if ON.
When OFF, disables local sensor if a remote sensor
is enabled.
PROGRAM
RUN
SET
and SET
(hold for approx.
3 seconds)
TIME
DAY
TIME
(Heat Pump ONLY)
FWD
TIME
FWD
TIME
FWD
TIME
FWD
FWD
TIME
FWD
TIME
FWD
TIME
TIME
FWD
FWD
TIME
FWD
6 SET CYCLE AUX
(06)
1 to 40
9 HEAT FAN DELAY OFF
(00)
0 to 127 seconds
10 PUMP
(ON)
OFF
11 COMP LOCK
(OFF)
ON
7 COOL FAN DELAY OFF
(00)
0 to 127 seconds
8
4
4
4
4
4
6
6
6
7
6
6
4
6
6
6
6
6 FAN DELAY ON
(01)
1 to 30 seconds
Selects time delay for fan ON. Applies only to
compressor stages for heat pump or COOL.
Selects time delay for COOL fan OFF.
Selects AUXILIARY stage anticipation adjustment.
(Heat Pump ONLY)
Selects time delay for HEAT fan OFF only when
ELECT HEAT FAN (Step 3) is ON.
Fossil Fuel Kit Alternative option. Turns compressor
OFF if Auxiliary is ON for longer than one minute.
(Heat Pump 1 & 2)
Selects compressor short-cycle protection enabled
or OFF.*
TIME
(Heat Pump ONLY)
TIME
(Heat Pump ONLY)
FWD
TIME
FWD
TIME
FWD
TIME
FWD
FWD
TIME
TIME
FWD
Step Press Button(s) Displayed (Factory Default) Press or to select: COMMENTS
See
Page
NOTE: You must be in the User
Configuration Menu to enter the
Installer Menu. Press TIME
FWD
and TIME
BACK
at same time.