White Rodgers 50a55-286 Thermostat User Manual


 
2
SPECIFICATIONS
ELECTRICAL RATINGS [@ 77°F (25°C)]:
Input Voltage: 25 VAC 50/60 Hz
Max. Input Current @ 25 VAC: 0.45 amp
Relay Load Ratings:
Valve Relay: 1.5 amp @ 25 VAC 50/60 Hz 0.6 pf
Ignitor Relay: 6.0 amp @ 120 VAC 50/60 Hz
(resistive)
Flame Current Requirements:
Minimum current to insure flame detection: 1 µa DC*
Maximum current for non-detection: 0.1 µa DC*
Maximum allowable leakage resistance: 100 M ohms
*Measured with a DC microammeter in the flame probe
lead
OPERATING TEMPERATURE RANGE:
-40° to 175°F (-40° to 80°C)
HUMIDITY RANGE:
5% to 93% relative humidity (non-condensing)
MOUNTING:
Surface mount multipoise
Timing Specs: (@ 60 Hz**)
maximum
Flame Establishing Time: 0.8 sec
Flame Failure Response Time: 2.0 sec
** At 50 Hz, all timing specifications should be increased
by 20%
Gases Approved: Natural, Manufactured, Mixed, Liquid
Petroleum, and LP Gas Air Mixtures are all approved for
use.
TIMING SPECIFICATIONS
(All times are in seconds, unless noted otherwise)
PRE-PURGE
INITIAL IGNITOR
RETRY IGNITOR
IGNITION ACTIVATION
PERIOD
TRIAL FOR IGNITION
PERIOD
RETRIES
VALVE SEQUENCE
PERIOD
INTERPURGE
POST-PURGE
LOCKOUT TIME
DELAY TO HEAT ON
DELAY TO HEAT OFF*
DELAY TO COOL ON
DELAY TO COOL OFF
AUTO RESET
HUMIDIFIER
ELECTRONIC AIR
CLEANER
0
17
28
5
7
2 times
21
15
15
200
30
60/90/
120/180
0
45
60 minutes
YES
YES
50A55-286
* This time will vary depending on option switch
position. The control is factory-set at 60 sec.
delay to heat off. See OPERATION section
for further information.