White Rodgers 24A5X Fan User Manual


 
DEFINITIONS
SPECIFICATIONS
INSTALLATION
U.L. Ambient Rating:
-20° to +165°F (-29° to +74°C)
Terminals:
Dual 1/4" male quick-connect for combination
AC Electrical Ratings:
Main Switch - (Terminals designated “M”)
Maximum Load: 25A at 240 VAC
Combined Load: 22A non-inductive plus 4A
inductive at 240 VAC or 20.8A non-inductive
plus 5.2A inductive at 240 VAC
Auxiliary Switch - (Terminals designated “A”)
1.0A at 30 VAC non-inductive
Bimetal Heater - (terminals designated “H”)
Input: 24 VAC 60 Hz 0.16A
All wiring must conform to local and national electrical codes and ordinances.
The terminal markings are equivalent to most other manufacturers' types. Follow the original equipment manufac-
turers' recommendations for proper wiring.
Wiring
MAIN CONTACTS: These are the load contacts and are
identified by the terminals designated “M”. The M1-M2
contacts will always be the first set of contacts to close
and the last set to open. The M3-M4 contacts will always
be the second set of contacts to close and the second-to-
last set of contacts to open. The M5-M6 contacts will
always close last and open first.
AUXILIARY CONTACTS: These contacts are identified
by terminals designated “A”. During the ON cycle, these
contacts complete the control circuit to subsequent se-
quencers when more than one is required. These con-
tacts will close after all main contacts have closed and will
open before any of the main contacts open.
FAN INTERLOCK: When multiple sequencers are used,
U.L. requires a fan interlock circuit which will guarantee
that the fan will stay on until all heating elements are de-
energized. The fan interlock circuit must be the first set of
contacts to close and will normally be marked “M1-M2”.
The sequencer may be mounted in any position and
location provided that the temperature does not exceed
the U.L. ambient rating.
Follow the original equipment manufacturers' recom-
mendations for the proper location.