White Rodgers 1F85-0477 Thermostat User Manual


 
6
INSTALLER/CONFIGURATION MENU
With thermostat in Heat, Cool or Auto, in normal operation, press the Menu button for at least 5 seconds. The display will show
item #1 in the table below. Press Menu button to advance to the next menu item. Press
or to change an item option.
INSTALLER/CONFIGURATION MENU
MENU
REF.
HP SS
PRESS
BUTTON
DISPLAYED
(FACTORY DEFAULT)
Press
or to
select from listed options
COMMENTS
1 1 1 MENU Lk (OFF) L Selects Keypad Lockout.
(Not available on earlier models)
MENU 0 001 to 999 Selects Keypad lockout combination number
2 2 2 MENU (MS 2) HP 1, HP 2, SS 1 Selects Multi-Stage (MS 2 No Heat Pump),
Heat Pump 1 (HP 1, 1 compressor),
or Single Stage (SS 1), Heat Pump 2 (HP 2, 2
compressor or 2 speed compressor)
3 3 3 MENU (GAS) for SS or MS
(ELE) for HP
ELE GAS setting: furnace controls the blower
ELE setting: thermostat controls the blower
4 4 4 MENU CS (0)
(Disabled)
1, 2, 3, 4, 5, 6 Selects Cool Savings
Value 1 (low) to 6 (high), Value 0 Disables Feature
5 5 5 MENU E (On) OFF Selects Energy Management Recovery (EMR)
On or OFF.
6 6 MENU CR Heat (ME) SL, FA Adjustable Anticipation:
Selects heating cycle rate for MS or SS
7 6 MENU CR Heat Pump
(ME)
SL, FA Adjustable Anticipation (Heat Pump) (only
when heat pump is selected in #1)
8 7 7 MENU CR Cool (ME)
or
CR Emer (FA)
SL, FA
SL
Adjustable Anticipation: Selects the cycle rate for
cooling (only when MS 2 or SS 1 is selected in
item 1.) or Selects the cycle rate for Emergency
mode and Auxiliary stage if Heat Pump is
selected in item 1.
9 8 8 MENU CL (OFF) CL On Compressor Lockout Time
10 9 9 MENU Heat Auto
Cool Off
Heat Cool Off,
Heat Off with Fan icon,
Heat Off without Fan icon
Cool Off, Auto Off
System Mode Configuration
with Automatic Changeover capability
11 10 10 MENU dL (On) dL OFF Selects Display Light On or OFF
12 11 11 MENU 0
(current temperature)
1 HI, 2 HI, 3 HI, 4 HI,
1 LO, 2 LO, 3 LO, 4 LO
Adjustable Ambient Temperature Display
13 12 12 MENU
°F °C
Selects Fahrenheit/Celsius Temperature Display
14 13 13 MENU L Heat
(90)
L 62 to L 89 Selects Limited HEAT Range
15 14 14 MENU L Cool
(45)
L 46 to L 82 Selects Limited COOL Range
16 15 15 MENU P7 P3 Defaults for 7 day programming (P7) or 5/1/1
day programming (P3) is available
17 16 16 MENU Heat AS (On) OFF Automatic Schedule for heat mode.
18 17 17 MENU Cool AS (On) OFF Automatic Schedule for cool mode.
19 18 MENU Heat FA (On) OFF Fast Heat option may be disabled by
selecting OFF. NA to SS config.
20 19 MENU Cool FA (On) OFF Fast Cool option may be disabled by
selecting OFF. NA to SS config.
NA to Heat only system.
21 20
18
MENU CA (OFF)
On
Selects active Comfort Alert On or OFF.
Require CA II Module. (Not available on earlier
models)
22 21 19 MENU dS (On) OFF Selects Automatic daylight Savings Time option
On or OFF.
23 22 20 MENU Change Filter (OFF) On Selects Filter Change-out Indicator On or OFF.
MENU Change Filter (200 h) 25-1975 h Change Filter time in 25 hour increments. This
menu only appears if On is selected in above.
24 23 21 MENU Cool On (o) Heat On (b) Selects operation of the reversing valve terminal
(O/B) output as an O or B terminal.
25 24 22 RUN Returns to Normal Operation