Troubleshooting — control module lights (cont.)11c
Turn off power to the boiler at service switch or breaker.
Wait at least 45 seconds.
Turn on power to boiler.
Restart boiler, following Operating instructions in this
manual (Section 9c).
Look through the pilot inspection port to see if the pilot is
burning during the prepurge period (first 30 seconds of
operation).
Is pilot burning during prepurge period?
CHART 4 FLAME & POWER lights flashing
Electrical shock hazard — Wherever you see TURN OFF POWER , follow the instructions. Failure to follow
instructions could result in severe personal injury, death or substantial property damage.
Leave main manual gas valve closed.
Turn off power to boiler at service switch or breaker.
Wait at least 45 seconds.
Turn on power to boiler.
Restart boiler, following Operating instructions in this
manual (Section 9c).
Do FLAME and POWER lights still flash?
Boiler should now
operate normally.
Original flashing
FLAME light
caused by gas
valve not
operating properly.
See normal
sequence of
operation,
Figure 30,
page 37.
Replace gas valve.
Retest boiler.
Are FLAME and POWER lights flashing?
No
Yes
No Yes
Are manual main shutoff valve and gas valve open?
Replace control module.
Retest.
— Usually indicates flame sensed when it shouldn't be there —
YesNo
TURN OFF POWER
to boiler at service switch
or breaker.
Open main manual gas
valve.
Turn on power to boiler
at service switch or
breaker.
Restart boiler per lighting
instructions.
Perform start-up
procedures in boiler
manual to verify proper
operation.
Allow boiler to continue cycling.
Are FLAME & POWER lights flashing?
No
Yes
No
Yes
Replace control
module.
Retest.
Replace control
module.
Retest.
Boiler may now be
operating
normally.
Perform start-up
procedures in
boiler manual to
verify proper
operation.